- Hydro unit / Hydro unit HT

If an error occurs during the operation, The Wired Remote controller show that Error mode.
- When ERRORS related to cooling and heating operation occur, the ventilator (ERV) continues to perform in normal operation.
- When ERRORS related to a ventilator (ERV) occur, it stops operating.
■ ERROR CODE DISPLAY on Wired remote controller
Error code
Communication error between DVM Hydro unit / Hydro unit HT and outdoor unit
E101
(When DVM Hydro unit / Hydro unit HT is having trouble with receiving data from outdoor unit)
Communication error on outdoor unit
E102
(When outdoor unit is having trouble sending data to DVM Hydro unit / Hydro unit HT)
E110
Communication error between DVM Hydro unit / Hydro unit HT and Control Kit (Detection from the Control Kit)
E121
Error on room temperature sensor of DVM Hydro unit / Hydro unit HT (Short or Open)
E122
Error on EVA IN sensor of DVM Hydro unit / Hydro unit HT (Short or Open)
E123
Error on EVA OUT sensor of DVM Hydro unit / Hydro unit HT (Short or Open)
E128
EVA IN sensor of DVM Hydro unit / Hydro unit HT is detached
E129
EVA OUT sensor of DVM Hydro unit / Hydro unit HT is detached
E130
EVA IN and EVA OUT sensor of DVM Hydro unit / Hydro unit HT is detached
E151
Error due to opened EEV of DVM Hydro unit / Hydro unit HT (2nd detection)
E152
Error due to closed EEV of DVM Hydro unit / Hydro unit HT (2nd detection)
E161
Mixed operation mode error
E162
EEPROM error
E163
EEPROM option setting error
E177
Check the water circulating
E185
Cross wiring error (When power line is connected to communication line of DVM Hydro unit / Hydro unit HT)
E198
Error due to disconnected Thermal Fuse (When the temperature of terminal block is increases)
E601
Communication error between remote controller and the DVM Hydro unit / Hydro unit HT
E602
Communication error between master and slave remote controller
E604
Tracking error between remote controller and the DVM Hydro unit / Hydro unit HT
E618
Error due to exceeding maximum numbers of Hydro unit installation (16 units)
E627
Error due to exceeding maximum numbers of wired remote controller installation (2 units)
E633
Error caused by installing mixed models
E653
Remote controller's temperature sensor is disconnected or has problem
E654
Data error on remote controller (Memory read/write error)
E901
Error on the sensor of water inlet pipe (Short or Open)
E902
Error on the sensor of water outlet pipe (Short or Open)
E904
EEPROM option setting error
E907
Error due to pipe rupture protection
E908
Error due to freeze prevention(Re-operation is possible)
E909
Error due to freeze prevention(Re-operation is impossible)
E910
Water temperature sensor on water outlet pipe is detached
E911
Flow switch off error, When the switch is turned off within 10 seconds after a pump starts its operation(Re-operation is possible)
E913
Six times detection for Flow Switch Error(Re-operation is not possible)
E914
Error due to incorrect thermostat connection
E915
Error on DC fan(Non-operating)
E917
Water Tank Sensor Configutation Error