High Pressure Sensor Error (Open/Short) - Samsung AM017HN1DEH/EU Service Manual

System
Hide thumbs Also See for AM017HN1DEH/EU:
Table of Contents

Advertisement

4-4-49 High Pressure sensor error (Open/Short)

Outdoor unit display
Indoor unit display
Criteria
∙ Refer to the judgment method below.
Cause of problem
∙ Disconnection or breakdown of relevant sensor.
1. High Pressure sensor Open/Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open/Short error will occur if the input voltage standard range of 0.5V ~ 4.95V is exceeded.
2. Inspection Method
Did the High Pressure
sensor connector get disconnected
from the PCB?
Is there refrigerant inside the set?
(Please check by connecting the menu folder gauge
to the service valve)
Out of the PCB High Pressure
sensor terminals, is there voltage between
pins 3 and 4 5V?
Replace High Pressure sensor
Samsung Electronics
Yes
Yes
Yes
No
Please re-inspect after connecting
the connector to the PCB
No
Refill refrigerant after vacuum
No
The mark is the 1st pin on the PCB.
Troubleshooting
Replace PCB
373