Samsung AM017HN1DEH/EU Service Manual page 319

System
Hide thumbs Also See for AM017HN1DEH/EU:
Table of Contents

Advertisement

Troubleshooting
Diagnosis and Adjustment (Error Code)
Error code related to the Communications / Settings / HW
CODE
E-211
When single indoor unit uses 2 MCU ports that are not in series.
If the rotary switch (on the MCU) for address setting of the indoor unit has 3 or more of the same
E-212
address
When total number of indoor units assigned to MCU is same as actual number of installed indoor
E-213
units but there is indoor unit that is not installed even though it is assigned on MCU
When number of MCU is not set correctly on the outdoor unit or when two or more MCU was
E-214
installed some of them have the same address
E-215
When two different MCU's have same address value on the rotary switch
E-216
When indoor unit is not installed to a MCU port but the switch on the port is set to On.
hen indoor unit is connected to a MCU port but indoor unit is assigned to a MCU and the switch
E-217
on the port is set to Off
When there's at least one or more actual number of indoor unit connection compared to number
E-218
of indoor units assigned to MCU
E-219
Error on temperature sensor located on MCU intercooler inlet (Short or Open)
E-220
Error on temperature sensor located on MCU intercooler outlet (Short or Open)
E-221
Error on outdoor temperature sensor of outdoor unit (Short or open)
E-231
Error on COND OUT temperature sensor of main outdoor unit (Short or Open)
E-241
COND OUT sensor is detached
E-251
Error on discharge temperature sensor of compressor 1 (Short or Open)
E-257
Error on discharge temperature sensor of compressor 2 (Short or Open)
E-262
Discharge temperature sensor of compressor 1 is detached from the sensor holder on the pipe
E-263
Discharge temperature sensor of compressor 2 is detached from the sensor holder on the pipe
E-266
Top sensor of compressor 1 is detached
E-267
Top sensor of compressor 2 is detached
E-269
Suction temperature sensor is detached from the sensor holder on the pipe
E-276
Error on top sensor of compressor 1 (Short or Open)
E-277
Error on top sensor of compressor 2 (Short or Open)
E-291
Refrigerant leakage or error on high pressure sensor (Short or Open)
E-296
Refrigerant leakage or error on low pressure sensor (Short or Open)
E-308
Error on suction temperature sensor (Short or Open)
322
(cont.)
Explanation
Samsung Electronics

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Am022hn1deh/euAm028fn1deh/euAm022fn1deh/euAm036fn1deh/euAm071jn1deh/euAm056fn2deh/eu ... Show all

Table of Contents