Samsung AM017HN1DEH/EU Service Manual page 11

System
Hide thumbs Also See for AM017HN1DEH/EU:
Table of Contents

Advertisement

Indoor Unit (cont.)
Wind-free 1way cassette type (cont.)
Model
Power Supply
1)
Mode*
Cooling*
Capacity
Performance
Heating*
Condensate
(with High fan speed)
Input
Power
Running Current
4)
Sound Level Sound Pressure *
Type
Model
Fan
Motor
Type
Output
Air Flow Rate
Type
Refrigerant
Control Method
Temperature Control
Safety Devices
Liquid (Flare)
Piping
Gas (Flare)
Connections
Drain (Quick Lock)
Net Weight
Weight
Shipping Weight
Net Dimensions (W x H x D)
Dimensions
Shipping Dimensions (W x H x D)
Model
Net Weight
Panel Size
Shipping Weight
Net Dimensions (W x H x D)
Shipping Dimensions (W x H x D)
Auto Restart
Auto Swing
Functions
Group/Individual Control
External Contact Control
Trouble Shooting by LED
Installation Manual
Operation Manual
Pattern Sheet for Installation
Standard
Flexible Drain Hose
Accessories
Filter / Safety Grille
Drain Pump
(Pumping speed, lift)
Wireless Remote Controller
Optional
Wired Remote Controller
Accessories
External Contact Interface Module
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.
Samsung Electronics
AM017NN1PEH*
ø/V/Hz
1/220~240/50
HP/HR
kW
1.70
2)
Btu/h
5,800
kW
1.90
3)
Btu/h
6,500
Liters/h
-
W
24.0
A
0.14
dB(A)
46
-
Cross flow fan
-
SIC-41CVJ-F127-2
-
BLDC
W
27 x 1
m3/min
4.80/4.30/4.10
-
R410A
-
EEV
-
Micom & Thermistors
-
Fuse
ø, mm
6.35
ø, mm
12.70
ø, mm
VP20 (OD 26,ID 20)
kg
8.0
kg
10.5
mm
740 x 135 x 360
mm
895 x 223 x 435
-
PC1MWFMAN
kg
2.6
kg
3.8
mm
960 x 35 x 420
mm
1003 X 482 X 112
-
O
-
O
-
O
-
O
-
O
-
O
-
X
-
O
-
O
-
Filter (Washable)
ℓ/h,mm
24/750
-
AR-EH03E
-
MWR-WE13N
-
MIM-B14
AM022NN1PEH*
AM022NN1DEH*
1/220~240/50
1/220~240/50
HP/HR
HP/HR
2.20
2.20
7,500
7,500
2.50
2.50
8,500
8,500
-
-
25.0
40.0
0.15
0.20
47
47
Cross flow fan
Cross flow fan
SIC-41CVJ-F127-2
Y4S476B041L
BLDC
Feedback SSR
27 x 1
17 x 1
5.10/4.60/4.30
6.00/5.00/4.00
R410A
R410A
EEV
EEV
Micom & Thermistors
Micom & Thermistors
Fuse
Fuse
6.35
6.35
12.70
12.70
VP20 (OD 26,ID 20)
VP20 (OD 26,ID 20)
8.0
10.0
10.5
12.8
740 x 135 x 360
970 x 135 x 410
895 x 223 x 435
1,173 x 231 x 487
PC1MWFMAN
PC1NWFMAN
2.6
4.3
3.8
6.3
960 x 35 x 420
1198 x 35 x 500
1003 X 482 X 112
1262 X 568 X 124
O
O
O
O
O
O
O
O
O
O
O
O
X
X
O
O
O
O
Filter (Washable)
Filter (Washable)
24/750
24/750
AR-EH03E
AR-EH03E
MWR-WE13N
MWR-WE13N
MIM-B14
MIM-B14
Product Specifications
AM028NN1DEH*
AM036NN1DEH*
1/220~240/50
1/220~240/50
HP/HR
HP/HR
2.80
3.60
9,600
12,300
3.20
4.00
10,900
13,600
-
-
45.0
50.0
0.23
0.25
50
55
Cross flow fan
Y4S476B041L
Y4S476B041L
Y4S476B041L
Feedback SSR
Feedback SSR
17 x 1
17 x 1
7.00/6.00/5.00
8.00/7.00/6.00
R410A
R410A
EEV
EEV
Micom & Thermistors
Micom & Thermistors
Fuse
Fuse
6.35
6.35
12.70
12.70
VP20 (OD 26,ID 20)
VP20 (OD 26,ID 20)
10.0
10.0
12.8
12.8
970 x 135 x 410
970 x 135 x 410
1,173 x 231 x 487
1,173 x 231 x 487
PC1NWFMAN
PC1NWFMAN
4.3
4.3
6.3
6.3
1198 x 35 x 500
1198 x 35 x 500
1262 X 568 X 124
1262 X 568 X 124
O
O
O
O
O
O
O
O
O
O
O
O
X
X
O
O
O
O
Filter (Washable)
Filter (Washable)
24/750
24/750
AR-EH03E
AR-EH03E
MWR-WE13N
MWR-WE13N
MIM-B14
MIM-B14
5

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Am022hn1deh/euAm028fn1deh/euAm022fn1deh/euAm036fn1deh/euAm071jn1deh/euAm056fn2deh/eu ... Show all