Delta Compact Drive MS300 IP66/NEMA 4X Series User Manual page 47

Table of Contents

Advertisement

Recommended models or dimensions for ferrule terminals
Wire Gauge
Manufacturer
0.25 mm
2
PHOENIX CONTACT
[24 AWG]
0.34 mm
2
PHOENIX CONTACT
[22 AWG]
0.5 mm
2
PHOENIX CONTACT
[20 AWG]
Recommended specifications and models for ferrules:
CRIMPFOX 10S - 1212045, Manufacturer: PHOENIX CONTACT
DNT13-0101, Manufacturer: DINKLE
Terminals
Terminal Function
Digital control signal common
+24 V
(Source)
MI1
Multi-function input 1–7
MI7
Chapter 6 Control Circuit Terminals MS300 (IP66 / NEMA 4X)
Model Name
A (MAX)
AI 0,25- 8 YE
12.5
AI 0,34- 8 TQ
12.5
AI 0,5 - 8 WH
14
+24 V±10 % 100 mA
Refer to Pr.02-01–02-07 to program the multi-function
inputs MI1–MI7.
Source Mode
ON: the activation current is 3.3 mA ≥ 11 V
OFF: cut-off voltage ≤ 5 V
Sink Mode
ON: the activation current is 3.3 mA ≤ 13 V
OFF: cut-off voltage ≥ 19 V
 When Pr.02-00 = 0, MI1 and MI2 can be
programmed.
 When Pr.02-00 ≠ 0, the function of MI1 and MI2 is
according to Pr.02-00 setting.
 When Pr.02-07 = 0, MI7 is pulse input with
maximum frequency 33 kHz (See Pr.10-00,
Pr.10-02, Pr.10-16).
6-5
Figure 6-8
B (MAX) D (MAX) W (MAX)
8
2.6
8
3.3
8
3.5
Default (NPN mode)
DC
DC
Unit: mm
1.1
1.3
1.4
Table 6-2
DC
DC

Hide quick links:

Advertisement

Table of Contents
loading