LED Indicator & Troubleshooting
There are two LED indicators on CMM-EIP01: POWER LED and LINK LED. POWER LED
displays the status of the working power, and LINK LED displays the connection status of the
communication.
LED Indicators
LED
POWER
Green
LINK
Green
Troubleshooting
Abnormality
POWER LED off
LINK LED off
No communication
card found
Fail to open
CMC-EIP01 setup
page
Able to open
CMC-EIP01 setup
page but fails to
utilize webpage
monitoring
Fails to send e-mail
Chapter 8 Optional Cards  MS300 (IP66 / NEMA 4X)
Status
On
Power supply in normal status
Off
No power supply
Network connection in normal
On
status
Flashes
Network in operation
Off
Network not connected
Cause
The AC motor drive is not
powered.
The CMM-EIP01 is not
connected to the AC motor
drive.
The CMM-EIP01 is not
connected to network.
Poor contact to the RJ45
connector
The CMM-EIP01 is not
connected to the network.
The PC and the CMM-EIP01
are in different networks and
blocked by network firewall.
The CMM-EIP01 is not
connected to the network.
Incorrect communication
setting in DCISoft
The PC and the CMM-EIP01
are in different networks and
blocked by network firewall.
Incorrect network setting in
the CMM-EIP01
Incorrect network setting in
the CMM-EIP01
Incorrect mail server setting
Indication
No action is required.
Check the power supply.
No action is required.
No action is required.
Check if the network cable is
connected.
Check if the AC motor drive is powered, and if the
power supply is normal.
Make sure the CMM-EIP01 is connected to the AC
motor drive.
Make sure the network cable is correctly connected
to network.
Make sure the RJ45 connector is connected to the
EtherNet port.
Make sure the CMM-EIP01 is connected to the
network.
Search by IP or set up relevant settings using the
AC motor drive keypad.
Make sure the CMM-EIP01 is connected to the
network.
Make sure the communication setting in DCISoft is
set to EtherNet.
Set up with the AC motor drive keypad.
Check if the network setting for the CMM-EIP01 is
correct. For the Intranet setting in your company,
please consult your IT staff. For the Internet setting
at home, please refer to the network setting
instruction provided by your ISP.
Check if the network setting for the CMM-EIP01 is
correct.
Confirm the IP address for the SMTP-Server.
8-17
Corrective Action
Corrective Action