SPM Flex Gas Detector

Wiring and tubing

CAUTION
!
The safety of any system incorporating the SPM Flex gas detector is
the responsibility of the assembler of the system�
Position a permanently-installed SPM Flex gas detector so that it does
not interfere with access to the dedicated circuit breaker�
Use only the specified power adaptor/charger (see
page
63)�
Use the power adaptor/charger only in indoor applications�
NOTE
Do not wire relays and 4-20 mA in the same wire bundle�

Typical fixed installation topologies

The SPM Flex gas detector has flexible installation options that allow the user to
select the one most suitable for a specific application� The detector is supplied
with weather-sealed connectors for power, Ethernet, and communications
(for relays or 4-20 mA)� The Ethernet port can be replaced with an appropriate
connection in accordance with local codes (allowing the user to wire directly to
the terminal block)� Install each detector near a dedicated circuit breaker�
This table shows the default wiring configuration for the IP-rated communication
connector when installed by Honeywell Analytics� The relays are labeled for the
factory default but the configuration can be modified to have a single alarm and
separate faults�
Front View
1
7
6
2
8
3
5
4
*default pin configuration
Electrical connection is made via conduit directly to ports or via the connector
(see Figure 1,
"Connectors and ports" on page
suitable for conductors of 20 to 14 AWG (0�8 to 1�6 mm dia�)�
20
Relay/mA Terminal Connections
Relay/mA Terminal Connections
No.
Color
mA Sink
1
Red
Alarm2 NO
2
Black
Alarm2 COM Alarm2 COM
3
White
Alarm1 NO
4
Green
Alarm1 COM Alarm1 COM
5
Brown
Fault NO
6
Blue
Fault COM
7
Yellow
24 VDC +
8 White/Black 4-20 mA +
"Specifications" on
mA Source Isolated mA*
Alarm2 NO
Alarm2 NO
Alarm2 COM
Alarm1 NO
Alarm1 NO
Alarm1 COM
Fault NO
Fault NO
Fault COM
Fault COM
4-20 mA -
4-20 mA -
24 VDC -
4-20 mA +
10� The terminals used are