Honeywell SPM Flex User Manual page 51

Single point monitor gas detector
Hide thumbs Also See for SPM Flex:
Table of Contents

Advertisement

Display
Type Sub-
type
String
1
SPM Energized
2
Monitoring Started
3
Monitoring Stopped
4
Tape Advanced
5
Force mA Requested
6
mA Output Forced
7
mA Output Released
8
User Login
9
User Logged Out
10
Alarm/Fault Reset Request
11
Silent Buzzer Request
12
Enter Monitor Request�
13
Exit Monitor Request
14
Change CC Started
15
Inhibit Started
16
Inhibit End Request
17
4-20mA Calibration Started
18
Flow Characterization Started
19
Update Program Started
20
Update Program Failed
21
Update Program Success
22
Gas Related Configuration�
23
Non Gas Related Configuration�
24
Security Set Up Configuration
25
Optics Verification Started
26
Simulation Started
27
Force Relay Started
28
Force Relay End Request
29
Time Changed
30
Optics Auto Adjust Requested
31
Optics Auto Adjust Success
32
Optics Corrected
33
Mfg Service Mode
34
Electrical Noise
Instrument Fault/Maintenance Fault/Information Codes
Technical
Description
The microprocessor booted
Monitoring started
Monitoring stopped
A new windows was pulled� (remove for
production)
current loop forcing started
current loop forcing ended�
User logged-in successful�
User logged out manually or by timeout�
UI requests alarm/fault reset�
UI requests to shut off buzzer through Alarm/
fault reset menu�
UI requests to enter monitor
UI requests to out of monitor
UI initialize change CC sequence
UI initializes inhibit�
UI request to end inhibit�
UI initializes 4-20 calibration�
UI initializes flow char
User chose an update file to perform program
update�
Update program failed
Update program success
Gas related set up changed by UI�
Non-gas set up changed by UI�
Security set up changed
UI initialized optics verification sequence
UI requests to start simulation�
UI started force relay�
UI exited force relay function�
UI time set
Optics Auto-Adjust Success�
LED output dropped unexpectedly
UI has received commands to go into
manufacturing service mode
Optics block reports signal is noisy
SPM Flex Gas Detector
Meaning of
Probable
Parameter
Cause
N/A
N/A
N/A
N/A
zero
zero
N/A
User level which just logged in, 0
is lowest level
User level which just logged out,
0 is lowest level
N/A
N/A
N/A
N/A
N/A
which type of inhibit�
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
LED drive counts
1 – first SLDE
2 – second SLDE
3 – Reference Photodiode Shift
None
Failure code
Corrective
Action
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Start force relay
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Start optics auto-
N/A
adjust
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
51