Wiring

Guidelines

Follow local codes when sizing power wiring:
● Terminal Blocks, input, and communication: R/C (XCFR2) minimum 300 V, 10
A, 16-22 AWG solid or stranded
● Terminal blocks relays: R/C (XCFR2) minimum 300 V, 10 A, 14-22 AWG
stranded, 16-22 AWG solid
● All communication wiring should be shielded.
Network cabling can extend up to 2000 feet (609 m) per channel. Daisy chain
the network cable without T-taps. The 24V supply must be properly grounded in
accordance to all local electrical codes. Power wiring must be grounded with a
terminal ring at the screw and nut on the grounding plate inside the case.

Wiring Standalone monitor

Ground the shield at the main control panel. Connect the shield wire in the monitor
terminal block labeled "shield." Tape all exposed shield wire at the monitor to
insulate it from the enclosure.
Circuit Board Connections
Connect the power wiring to terminal J1, communication wiring to terminal J2,
and external devices (ventilators, strobes, etc. to relay terminals J5 or J6).