Introduction
Operating Environment
Operating temperature
Storage temperature
Humidity
Atmospheric pressure
Installation category
Pollution degree
Flammable catalytic versions: 10 to 90% RH. Operating the detector outside of this
range may result drift and a decrease detector accuracy.
Sensepoint XCL conforms to IP65, Type 4 (in accordance with NEMA 250) making it
suitable for use in Pollution Degree 3 environments.
Recommended Wall-Mounting Screws
Type
Size
Cable Gland
Inner knockout
Outer knockout
Gas Test Tubing
For a bump test, use urethane tubing with one of the below dimensions.
Select tubing appropriate for the gas being detected and length of
tubing. See Remote Gassing Connection on page 25.
Inner diameter
4 mm (0.16 in)
6 mm (0.24 in)
Gas
See Detector Parameters on page 40 for a full list of detectable gases,
ranges and other information.
12
All manuals and user guides at all-guides.com
NOTE
Install Sensepoint XCL in a sheltered location away from direct UV
light and rain.
−20 to 50 °C (−4 to 122 °F)
0 to 30 °C (32 to 86 °F)
0 to 99% (non-condensing)
90 to 110 kPa
II (UL/CSA/IEC/EN 61010-1)
2 (UL/CSA/IEC/EN 61010-1)
Countersunk, pan head
4 mm (No. 8) diameter × 25 mm (1 in) min.
M20 or ½ NPT
M25 or ¾ NPT
Outer diameter
6 mm (0.24 in)
8 mm (0.31 in)