FILLING IN WITH
E9_1
PELLETS
IN THE SUPPLY TUBE
FILLING IN WITH
E9_2
PELLETS
IN THE SUPPLY TUBE
DEFECT UPPER
E10
SENSOR IN THE
ACCUMULATION TANK
DEFECT LOWER
E11
SENSOR IN THE
ACCUMULATION TANK
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
Possible cause: Filling the flexible tube with pellets - variant_1
- when it is in operation reduced pellet supply over a period of
time in which it failed to return to the normal filling regime with
fulfilling (factory only active on CPPL 90)
Boiler status: Currently goes to OFF mode.
Troubleshooting: Check the fullfillness of the burner
gate,burner furnace,boiler furnace, and chimney , whether the
burner grate is well positioned in the burner (is not installed ON
the el. heater) - valid for CPPL 14-50), whether pellets are not
too humid, inadequate dimensions or quality pellets (for these
burner diameters 6 mm), possible holes on the flexible tube
pipe, too much pellet delivery/low rpm, incorrectly loaded filling
parameters, incorrect combustion air.
Possible cause: Filling the flexible tube with pellets - variant_2
- when it is in operation reduced pellet supply over a period of
time in which it failed to return to the normal filling regime with
fulfilling (factory only active on CPPL 90)
Boiler status: Currently goes to OFF mode
Troubleshooting: Check the fullness of the burner gate,
burner furnace, boiler furnace, and chimney, whether the
burner grate is well positioned in the burner (is not installed ON
the el. heater) - valid for CPPL 14-50), whether pellets are not
too humid, inadequate dimensions or quality pellets (for these
burner diameters 6 mm), possible holes on the flexible tube
pipe, too much pellet delivery/low rpm, incorrectly loaded filling
parameters, incorrect combustion air.
Possible cause: Interruption in cables between sensors and
control, control contacts, cold connection or defective sensor in
the accu tank upper part.
Boiler status: Departure to the Shutdown phase S7 (S7-1).
Troubleshooting: Call an authorized service person to check
the sensor location in the tank, check for sensor/cable damage,
check connections at the connectors, check the ohmic
resistance of the sensor.
Possible cause: Interruption in cables between sensors and
control, control contacts, cold connection or defective sensor in
the accu. tank lower part.
Boiler status: Departure to the Shutdown phase S7 (S7-1).
Troubleshooting: Call an authorized service person to check
the sensor location in the tank, check for sensor/cable damage,
check connections at the connectors, check the ohmic
resistance of the sensor.
Errors
81