The digital boiler controller
Hide thumbs Also See for Cm Pelet-set Touch 14:
Table of Contents

Advertisement

Heating configuration (markings on the display)
13.90. Configuration I-2-0
Temperatures: Tboiler: 80°C (80-90°C)
dTboiler: 10°C (5-15°C)
Tbuf: 80°C (70-80°C)
dTbuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
13.91. Configuration I-2-1
Temperatures: Tboiler: 80°C (80-90°C)
dTboiler: 10°C (5-15°C)
Tbuf: 80°C (70-80°C)
dTbuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
13.92. Configuration I-7-0
Temperatures:
Tboiler:
- Mode:
-> Heating+DHW: 80°C (80-90°C)
-> DHW: 70°C (75-80°C)
dTboiler:
- Mode:
- Heating+DHW: 10°C (5-15°C)
- DHW: 10°C (5-10°C)
68
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
1
4
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (5-50°C)
1
4
Tdhw: 50°C (10-70°C)
dTdhw: 5°C (5-50°C)
Tbuf min.: 20°C (5-85°C)
20
2
4
Tdhw:
- Mode:
- Heating+DHW: Tdhw=Tboiler=80°C
- DHW: Tdhw=Tboiler=70°C
dTdhw:
- Mode:
- Heating+DHW: 15°C (10-40°C)
- DHW: 15 (10-40°C)
EKO-CK P + Cm Pelet-set_Touch
3
bar
11
M
8
9
5
12
Circuit 1:
Const. temp. day: 60°C (20-90°C)
Const. temp. night: 60°C (20-90°C)
Day room temp.: 20°C (5-30°C)
Night room temp.: 20°C (5-30°C)
EKO-CK P + Cm Pelet-set_Touch
3
bar
11
8
M
9
5
12
Circuit 1:
Const. temp. day: 60°C (20-90°C)
Const. temp. night: 60°C (20-90°C)
Day room temp.: 20°C (5-30°C)
Night room temp.: 20°C (5-30°C)
EKO-CKB P + Cm Pelet-set_Touch
3
bar
8
M
9
5
Tbuf: 80°C (70-80°C)
dTbuf: 10°C (5-30°C)
dTbuf-off: 5°C (3-50°C)
17
10
18
19
17
13
14
10
18
19
M
11
10
12
16
16

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents