HIGH TEMPERATURE
E3
ON THE INLET TUBE
DEFECTIVE BOILER
E4
SENSOR
DEFECTIVE DHW
E5
SENSOR
LOSS OF FLAME
E6
DURING OPERATION
LOSS OF FLAME
E6_1
AFTER POWER LOSS
Technical manual - THE DIGITAL BOILER CONTROLLER Cm-Pelet set_Touch 14-90 kW
Possible cause: The temperature of the pellet flexible filling
tube on the burner is higher than 80° C.
Boiler status: Currently goes to OFF mode.
Troubleshooting: Possible fulfilling of the burner furnace and
flexible tube due to incorrectly adjusted combustion air,
incorrectly tuned delivery parameters, inadequate dimensions
or pellet quality, possible hole on the flexible tube or fall of the
flexible tube from the delivery tube, possible fan stopage,
possible impassable flue gas passages in boiler and chimney.
Possible cause: Break in the cables between the sensor and
control, control contacts, cold connection or defective boiler
sensor.
Boiler status: departure to shutdown mode.S7 (S7-1).
Troubleshooting: Call an authorized service person to check
the sensor location in the tank, check for sensor/cable damage,
check connections at the connectors, check the ohmic
resistance of the sensor.
Possible cause: Break in the cables between the sensor and
control, control contacts, cold connection or defective boiler
sensor.
Boiler status: departure to shutdown mode S7 (S7-1). If the
user turns off the DHW fault stops and the boiler can start.
Troubleshooting: Call an authorized service person to check
the sensor location in the tank, check for sensor/cable damage,
check connections at the connectors, check the ohmic
resistance of the sensor.
Possible cause: The photocell does not see the flame in the
burner furnace.
Boiler status: Currently goes to OFF mode.
Troubleshooting: Check that the fault is caused by the loss of
pellets (in the tank/transporter), the congestion of the
transporter motor, the spiral of the transporter, the foreign body
in the transporter, the improper supply, the supply of too humid
pellets, the burning of the burner grate to the remains of pellet
combustion or the scorching of the photocell.
Possible cause: The photocell does not see the flame during
the burner operation in the burner furnace, before which the
current has disappeared in one of the burner stages except
"OFF", "A0" and "S7-3".
Boiler status: departure to shutdown mode S7 (S7-1).
Troubleshooting: Check that the fault is caused by the loss of
pellets (in the tank / transporter), faulty feeding ,feeding of the
too humid pellets, the burning of the burner grate to the
remains of pellet combustion or the scorching of the photocell.
Clean grate and burner.
Errors
79