Basic Pass/Fail Smoke Test - VESDA LaserSCANNER VLS-200 Installation Manual

Table of Contents

Advertisement

LaserSCANNER Installation Manual

8.4 Basic Pass/Fail Smoke Test

Note: This test verifies the detector will sense smoke. It does not replace any appropriate
commissioning test. Use the table below to perform this test by using one of the
following devices.
Procedure
Display Module
• Press the Isolate
Isolate the
Detector.
button located on
the Display.
• Check the Isolated
indicator lights up.
• Scan starts
Inject Smoke
into any one
• Sounding device on
of the
Detector beeps.
sampling air
• Red LEDs on front
pipes and
panel lights up.
observe the
following
• Smoke bar graph
events.
indicator lights up
showing smoke
level.
• 2 digit indicator
shows smoke
intensity level when
Smoke Level is
selected.
• Press the Reset
After the
smoke has
button once to clear
cleared,
the alarms and
Reset the
various fault
Detector to
indicators.
clear the
alarms.
• Press the Isolate
De-Isolate the
detector.
button once.
• The Isolated
indicator goes off.
22
LCD Programmer
• Select Setup by Zone ↵
Zone Number ↵ Detector
↵ Zone Control ↵ Isolate
Start ↵
• Select Setup by Zone ↵
Zone Number ↵ Detector
↵ Status ↵ and check
the detector is Isolated.
• Select Setup by Zone ↵
Zone Number ↵ Detector
↵ Status ↵ and check
the smoke level value.
• Alarms reported in
Status menu.
• Select Setup by Zone ↵
Zone Number ↵ Detector
↵ Zone Control ↵ Reset
Reset ↵
• Select Setup by Zone ↵
Zone Number ↵ Detector
↵ Zone Control ↵ Isolate
Stop ↵
• Select Setup by Zone ↵
Zone Number ↵ Detector
↵ Status ↵ and check
the Isolated alarm is
cleared.
VESDA
PC Programmer
• Select Device Tree from
the View menu.
• Select the detector to be
Isolated from the Device
Tree window.
• Click on the Isolate icon
or Isolate Zone
command from the
Zone menu.
• View Active Events list
for response to
Isolation.
• Sounding device on the
Detector beeps.
• Smoke alarm displays
on the Active Events
List window.
• Click on the Reset icon
or select the Reset
command from the
Zone menu.
• Select the Device Tree
command from the View
menu.
• Click on the detector to
be De-Isolated from the
Device Tree window.
• Click on the De-Isolate
icon or select the De-
Isolate Zone command
from the Zone menu.
• View Active Events list
for the Isolated alarm to
clear from the list.