Ups Alive Check Function - Huawei UPS5000-E-FM Series User Manual

Hide thumbs Also See for UPS5000-E-FM Series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Figure 4-104 Setting the MDU IP address and SSL encrypted transmission mode on the RCCMD
client
Step 2 On the MDU WebUI, choose Config. > RCCMD, and set RCCMD function to Enable.
Step 3 On the WebUI of the MDU, the SSL encryption is set to Enable by default and does not need
to be set. If the RCCMD client is set to the unencrypted mode, you need to set the SSL
encryption to Disable on the server WebUI.
Step 4 Configure events. If you set the job type to RCCMD Message under Inverter on, specify the
IP address and port of the RCCMD client. The port is 6003 by default. If you need to modify
the port, modify the port on the RCCMD client at the same time to keep them the same. Enter
the message to be sent and set the message sending mechanism. For example, set it to
Immediately, once.
Step 5 On the Monitoring > Control page, start the UPS, and the inverter mode will be triggered.
Send the message to the RCCMD client, indicating that the inverter is on.
Step 6 On the RCCMD client, you can view messages through the View Event Log at the upper left
corner.
----End

4.2.6.3 UPS Alive Check Function

Context
Issue 06 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
176