Huawei UPS5000-E-FM Series User Manual page 149

Hide thumbs Also See for UPS5000-E-FM Series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Issue 06 (2019-12-13)
MUE05A connection
MUE05A connection status. Independent input signals can be enabled only when this
parameter is set to Enable.
Batter ground fault [BTG]
Enable or disable the battery grounding failure detection.
D.G. connection [GEN]
Enable or disable D.G. connection detection.
BCB connection [OL]
Enable or disable BCB connection detection.
Batter breaker [STA]
Enable or disable battery circuit breaker monitoring.
PDC output breaker [OUT]
Enable or disable PDC output circuit breaker monitoring.
PDC maintenance breaker [MT]
Enable or disable PDC maintenance circuit breaker monitoring.
BP/SYSMT Switch
If the BP/SYSMT switch is set to Enable, the port has dry contact signal access. Using
the port depends on the status of the BP/SYSMT switch.
BP/SYSMT switch function
If the BP/SYSMT switch is set to Enable, this parameter is displayed on the screen. Set
this parameter to determine whether the port is used to detect the status of the PDU
bypass input switch, or system maintenance switch.
SPD/SYSOUT Switch
If the SPD/SYSOUT switch is set to Enable, the port has dry contact signal access. How
a user uses the port depends on the status of the SPD/SYSOUT switch.
SPD/SYSOUT switch function
If the SPD/SYSOUT switch is set to Enable, this parameter is displayed on the screen.
Set this parameter to determine whether the port is used to detect the status of the PDU
input surge protector, or system output switch.
MUE06A connection
If this parameter is enabled, the mains and bypass backfeed protection is enabled.
MUS05A DO_1 Action
Control the status of the DO_1 dry contact on the MUS05A dry contact card.
MUS05A DO_2 Action
Control the status of the DO_2 dry contact on the MUS05A dry contact card.
MUS05A DO_3 Action
Control the status of the DO_3 dry contact on the MUS05A dry contact card.
MUS05A DO_4 Action
Control the status of the DO_4 dry contact on the MUS05A dry contact card.
MUE07A DO_1 Action
Control the status of the DO_1 dry contact on the MUE07 extended dry contact card.
MUE07A DO_2 Action
Control the status of the DO_2 dry contact on the MUE07 extended dry contact card.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
140

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-25k-fmUps5000-e-125k-fm

Table of Contents