Huawei UPS5000-E-FM Series User Manual page 36

Hide thumbs Also See for UPS5000-E-FM Series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Silk Screen
PARALLEL
BSC
Table 2-3 Indicator description
Indicator
NORMAL
ALM
FAULT
Functions
Issue 06 (2019-12-13)
Description
The PARALLEL port transmits parallel signals between racks.
The BSC port is used in a dual-bus system to synchronize output
frequencies and phases between UPS systems, ensuring that two buses
can switch with each other.
BSC cables are hot-swappable.
For a single UPS, the parallel cable is not needed.
Color
Green
Yellow
Red
As a control interface for the entire system, the ECM communicates with each module
and provides a bus to communicate with the dry contact card. The ECM ensures
equalized output currents between modules so that load power is equally shared.
Provides module running information for the MDU.
Controls the running of a single UPS5000 and a parallel system, and reports the
UPS5000 status information to other monitoring modules.
The system provides three types of CAN communication: monitoring CAN
communication, intra-rack parallel CAN communication, and inter-rack parallel CAN
communication.
Copyright © Huawei Technologies Co., Ltd.
Status
Description
Steady on
This ECM is the active ECM.
Blinking at
This ECM is the standby ECM and it is ready.
0.5 Hz
Off
This ECM is not ready or the CPLD of this
ECM is being upgraded.
Blinking at
The DSP of the ECM is being upgraded or not
4 Hz
configured.
Steady on
The ECM has a minor alarm, but it does not
need to be replaced.
Off
The ECM has no minor alarm or the DSP of the
ECM is being upgraded.
Steady on
The ECM has a critical alarm.
The ECM has no critical alarm or the DSP of the
Off
ECM is being upgraded.
2 Overview