UPS5000-E-(25 kVA-125 kVA)-FM
User Manual
Item
Cold start
Charger output power
Charge voltage
8.8 Output Electrical Specifications
Item
Output system
Voltage
Total harmonic distortion (THD)
Output PF
Transfer time
Output voltage unbalance
Overload capability
Issue 06 (2019-12-13)
UPS5000-E-125K-FM
In the case of a mains failure, batteries can start the
UPS to power loads.
(6250 W± 200 W) x N. The maximum charge power of
a power module is 6250 W± 200 W (the maximum
current is 10 A). N represents the number of power
modules in the rack.
Copyright © Huawei Technologies Co., Ltd.
Equalized charging voltage: 2.3–2.4 V/cell, 2.35
V/cell by default (30–42 batteries); 2.3–2.35 V/cell,
2.35 V/cell by default (44 batteries)
Float voltage: 2.23–2.3 V/cell, default: 2.25 V/cell
(30–44 batteries)
UPS5000-E-125K-FM
Three-phase, four-wire, and PE
380 V AC, 400 V AC, or 415 V AC (tolerance ± 1%)
(line voltage)
THDv ≤ 1% (full linear load)
1
0 ms (uninterruptible transfer)
≤ 20 ms (interruptible transfer)
Voltage unbalance: ± 3%, phase unbalance: 120± 2°
Inverter overload capability:
100% < load ≤ 110%: after 60 minutes, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
110% < load ≤ 125%: after 10 minutes, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
125% < load ≤ 150%: after 1 minute, transfer to
bypass mode if the bypass is normal or disconnect
output if the bypass is abnormal.
Load > 150% or in case of shout circuit, the
inverter can work for 200 ms .
8 Technical Specifications
220