Mains Input Electrical Specifications; Bypass Input Electrical Specifications; Battery Electrical Specifications - Huawei UPS5000-E-FM Series User Manual

Hide thumbs Also See for UPS5000-E-FM Series:
Table of Contents

Advertisement

UPS5000-E-(25 kVA-125 kVA)-FM
User Manual

8.5 Mains Input Electrical Specifications

Item
Input system
Rated input voltage
Input voltage range
Input frequency range
Input power factor
THDi

8.6 Bypass Input Electrical Specifications

Item
Rated input voltage
Input voltage range
Input system
Rated frequency
Frequency range
Input mode

8.7 Battery Electrical Specifications

Item
Number of batteries
Issue 06 (2019-12-13)
UPS5000-E-125K-FM
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
80–280 V AC (phase voltage)
40–70 Hz
> 0.99 at full load; > 0.98 at half load
≤ 3% (linear load); ≤ 5% (non-linear load)
UPS5000-E-125K-FM
380 V AC, 400 V AC, or 415 V AC (line voltage)
Upper threshold: +10%, +15% (default), +20%, +25%
(when the voltage system is 380 V AC)
Upper threshold: +10%, +15% (default), +20% (when the
voltage system is 400 V AC)
Upper threshold: +10% (default), +15% (when the voltage
system is 415 V AC)
Lower threshold: –10%, –15%, –20% (default), –30%,
–40%, –50%, –60%
Three-phase, four-wire, and PE
50 Hz / 60 Hz
± 6 Hz (adjustable, 0.5–6 Hz, ± 2 Hz by default)
The mains input and bypass input share a power source or
use different power sources
UPS5000-E-125K-FM
The UPS supports 30 to 44 batteries and is configured
with 32 batteries by default. The positive and negative
battery strings respectively contain 16 batteries. If 30
batteries are configured, the power is derated to 94%.
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
219