Belden Lumberg Automation LioN-P PROFINET IO-Link Master 0980 ESL 308-121 Manual

Belden Lumberg Automation LioN-P PROFINET IO-Link Master 0980 ESL 308-121 Manual

Hide thumbs Also See for Lumberg Automation LioN-P PROFINET IO-Link Master 0980 ESL 308-121:
Table of Contents

Advertisement

Manual
LioN-P PROFINET IO-Link Master
0980 ESL 308-121, 0980 ESL 398-121
0980 ESL 309-121, 0980 ESL 399-121
0980 ESL 109-121, 0980 ESL 199-121
0980 ESL 109-332, 0980 ESL 199-332
0980 ESL 109-122, 0980 ESL 199-122
0980 ESL 109-331, 0980 ESL 199-331
Manual LioN-P PROFINET IO-Link Master
Technical Support
Version 2.1 10/2017
support-automation@belden.com

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Lumberg Automation LioN-P PROFINET IO-Link Master 0980 ESL 308-121 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Belden Lumberg Automation LioN-P PROFINET IO-Link Master 0980 ESL 308-121

  • Page 1 0980 ESL 309-121, 0980 ESL 399-121 0980 ESL 109-121, 0980 ESL 199-121 0980 ESL 109-332, 0980 ESL 199-332 0980 ESL 109-122, 0980 ESL 199-122 0980 ESL 109-331, 0980 ESL 199-331 Manual LioN-P PROFINET IO-Link Master Technical Support Version 2.1 10/2017 support-automation@belden.com...
  • Page 2: Table Of Contents

    Contents Contents 1 About this manual 1.1 General information 1.2 Explanation of symbols 1.2.1 Use of danger information 1.2.2 Use of general information 1.3 Version information 2 Safety instructions 2.1 Intended use 2.2 Qualified personnel 3 Designations and synonyms 4 System description 4.1 PROFINET product features 4.2 IO port features 4.3 Integrated web server...
  • Page 3 Contents 5.2.2 Module 0980 ESL 1x9-121 5.2.3 Module 0980 ESL 1x9-332 5.2.4 Module 0980 ESL 1x9-122 5.2.5 Module 0980 ESL 1x9-331 5.3 Port assignments 5.3.1 PROFINET ports, M12 socket, 4-pin, D-coded 5.3.2 Power supply with M12 power L-coded 5.3.3 PROFINET and power supply with M12 Hybrid 5.3.4 I/O ports as M8 or M12 sockets 6 Starting operation 6.1 GSDML file...
  • Page 4 Contents 7 Bit assignment 7.1 Process data Status and Control module, slot 1/sub-slot 1 7.1.1 Digital IO mapping mode 1 (default mapping) 7.1.2 Digital IO mapping mode 2 (E2C compatibility) 7.2 Process data IO-Link ports, slot 1/sub-slot 2 - sub-slot 9 8 Diagnostics processing 8.1 Error in the system/sensor power supply 8.2 Error in auxiliary/actuator power supply...
  • Page 5 Contents 11.1 General 11.2 PROFINET protocol 11.3 Power supply for the module electronics/sensors 11.4 Power supply type B ports (auxiliary supply) 11.5 IO-Link Master Ports (X1 - X8, Ch. A/C/Q/ Pin 4) 11.5.1 Configured as a digital input 11.5.2 Configured as a digital output (except 0980 ESL 3x8-121) 11.5.3 Configured as an IO-Link port in COM mode 11.6 Digital inputs (X1 –...
  • Page 6: About This Manual

    Fax +49 (0) 23 55 / 5044-333 support-automation@belden.com www.lumberg-automation.com Belden Deutschland GmbH – Lumberg Automation™ – reserves the right to make technical changes or changes to this manual at any time without notice. Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 7: Explanation Of Symbols

    1 About this manual 1.2 Explanation of symbols 1.2 Explanation of symbols 1.2.1 Use of danger information Danger information is denoted as follows: Danger: Means that death, serious physical injury or substantial damage to property will occur if the required safety measures are not taken.
  • Page 8: Safety Instructions

    2.1 Intended use 2 Safety instructions 2 Safety instructions 2.1 Intended use The devices described in this manual are decentralized input/output assemblies on a PROFINET IO network. We adhere to all safety standards when developing, producing, testing, and documenting our products. When you adhere to the handling specifications and safety instructions described for the configuration, assembly, and correct operation, there should not normally be any risks for people or equipment.
  • Page 9: Qualified Personnel

    Only Belden Deutschland GmbH – Lumberg Automation™ – is permitted to make changes to the hardware or software of the products that go beyond the scope of this manual.
  • Page 10: Designations And Synonyms

    3 Designations and synonyms 3 Designations and synonyms LioN-P 30 LioN-P devices with a width of 30mm LioN-P 60 LioN-P devices with a width of 60mm Type A IO-Link port specification (Class A) Type B IO-Link port specification (Class B) I/O port X1 - X8 I/O port pin 4 (C/Q)
  • Page 11: System Description

    4 System description 4.1 PROFINET product features 4 System description LioN modules (Lumberg input/output Network) function as the interface in an industrial fieldbus system: They enable a central controller on the management level to communicate with the decentralized sensors and actuators on the field level.
  • Page 12 4.1 PROFINET product features 4 System description PROFINET IO Device RT LioN-P IO-Link master modules support PROFINET IO Device RT (real-time). This allows the transmission of time sensitive process data between network components in real-time communication. PROFINET specification V2.3, Conformance Class C (CC-C) LioN-P IO-Link master...
  • Page 13 4 System description 4.1 PROFINET product features The master modules use the DCP protocol to automatically assign IP addresses. LLDP The LLDP protocol is used to detect devices in the vicinity (neighborhood detection). SNMP The SNMP protocol handles network component monitoring and communication between the master and device.
  • Page 14: Io Port Features

    4.2 IO port features 4 System description 4.2 IO port features The master modules support the IO-Link standard v1.1. Parametrization of the IO-Link devices in PROFINET via Siemens IO_LINK_CALL function modules for Step7 and TIA Portal. Parametrization of the IO-Link devices via TMG IO-Link Device Tool >...
  • Page 15: Integrated Web Server

    4 System description 4.3 Integrated web server IO device parameterization IO-Link devices PROFINET parameterized via the Siemens function module IO_LINK_CALL for STEP 7 and the TIA Portal. You can see the status of a port by the color of the matching LEDs and their flash pattern.
  • Page 16: Other Features

    4.4 Other features 4 System description 4.4 Other features Interface protection The modules have reverse polarity, short-circuit and overload protection for all interfaces. Failsafe The modules support a failsafe function. This allows you to define the behavior of every single channel configured as an output in the case of an interruption or a loss of PROFINET communication.
  • Page 17: Product Overview

    4 System description 4.5 Product overview 4.5 Product overview The following IO-Link masters are available for the LioN-P system: Article Product Description Power & I/O ports number designation Ethernet ports 934 878 005 0980 ESL 308-121 LioN-P M12-60, PWR - M12 8x M12 A-coded IO-Link Master L-coded,...
  • Page 18 4.5 Product overview 4 System description Article Product Description Power & I/O ports number designation Ethernet ports 934 862 001 0980 ESL 109-331 LioN-P M12-30, PWR - M12 8x M12 A-coded Hybrid, IO-Link Master SP - PROFINET ETH – M12 934 964 001 0980 ESL 199-331 LioN-P M12-30,...
  • Page 19: Assembly And Wiring

    5 Assembly and wiring 5.1 General information 5 Assembly and wiring 5.1 General information Mount the module on a flat surface using 2 screws (M4x 25/30). The torque required here is 1 Nm. Use washers for all fastening methods as per DIN 125. Attention: The modules have a ground connection with an M4 thread for the conduction of interference currents and the EMC immunity.
  • Page 20: Outer Dimensions

    5.2 Outer dimensions 5 Assembly and wiring 5.2 Outer dimensions 5.2.1 Module 0980 ESL 3x8-121 & ESL 3x9-121 Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 21: Manual Lion-P Profinet Io-Link Master

    5 Assembly and wiring 5.2 Outer dimensions 5.2.2 Module 0980 ESL 1x9-121 Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 22: Module 0980 Esl 1X9-332

    5.2 Outer dimensions 5 Assembly and wiring 5.2.3 Module 0980 ESL 1x9-332 Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 23: Module 0980 Esl 1X9-122

    5 Assembly and wiring 5.2 Outer dimensions 5.2.4 Module 0980 ESL 1x9-122 Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 24: Module 0980 Esl 1X9-331

    5.2 Outer dimensions 5 Assembly and wiring 5.2.5 Module 0980 ESL 1x9-331 Attention: For U application: Be sure to use a UL-certified cable with a suitable evaluation to connect the devices (CYJV or PVVA). To program the control, please refer to the OEM information, and only use suitable accessories. Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 25: Port Assignments

    5 Assembly and wiring 5.3 Port assignments Only approved for interior use. Please note the maximum elevation of 2000 meters. Approved up to a maximum soiling level of 2. Warning: Terminals, housings field-wired terminal boxes or components can exceed temperatures of 60° C. Warning: For UL application (max.
  • Page 26: Power Supply With M12 Power L-Coded

    5.3 Port assignments 5 Assembly and wiring Port Signal Function PROFINET Transmit data plus Ports X01, X02 Receive data plus Transmit data minus Receive data minus Table 3: Assignment of ports X01, X02 Caution: Risk of destruction! Never connect the power supply to the data cables.
  • Page 27: Profinet And Power Supply With M12 Hybrid

    5 Assembly and wiring 5.3 Port assignments Power supply Signal Function (+24 V) Sensor/system power supply GND_U Ground/reference potential U GND_U Ground/reference potential U (+24 V) Auxiliary supply (electrically isolated) FE (PE) Functional ground Table 4: Power supply with M12-Power Attention: Only use power supply units for the system/sensor and actuator supply that correspond to PELV (Protective Extra Low Voltage) or SELV (Safety Extra Low Voltage).
  • Page 28: I/O Ports As M8 Or M12 Sockets

    5.3 Port assignments 5 Assembly and wiring Ether + Signal Function Power Supply PROFINET Transmit data plus Ports X01, X02 Receive data plus Transmit data minus Receive data minus GND_U Ground/reference potential GND_U GND_U Ground/reference potential GND_U (+24 V) Sensor/system power supply (+24 V) Auxiliary supply (electrically isolated)
  • Page 29 5 Assembly and wiring 5.3 Port assignments Figure 7: Schematic drawing IO port as M12 socket IO Link Type A IO Link Signal Function Type A IO Link sensor power supply +24 V IN-x Ch. B: Digital input (type 1) IO Link sensor supply GND_U Ch.
  • Page 30 5.3 Port assignments 5 Assembly and wiring IO Link Signal Function Type B IO Link sensor power supply +24 V 2L+ (U Ch. B: Auxiliary power supply (electrically isolated with respect to the sensor/system power supply) IO Link sensor supply GND_U Ch.
  • Page 31: Starting Operation

    6 Starting operation 6.1 GSDML file 6 Starting operation 6.1 GSDML file A GSD file in XML format is required to configure the LioN-P modules. All module variants are grouped in a single GSDML file. This can be downloaded from our homepage www.beldensolutions.com/en/Service/download_center/index.phtml.
  • Page 32: Configuration Of The Lion-P Profinet I/O Modules In Step

    6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 PROFINET name: Name not assigned IP address: 0.0.0.0 Subnet mask: 0.0.0.0 Device designations: 0980 ESL 109-121 0980 ESL 109-122 0980 ESL 109-331 0980 ESL 109-332 0980 ESL 308-121 0980 ESL 309-121 0980 ESL 199-121 0980 ESL 199-122...
  • Page 33: Assigning A Device Name To A Lion-P Module

    6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 1. Select the module in HW-Config and open the menu Edit > Object properties. In the dialog box that opens, you can then change the device name.
  • Page 34: Configuring The Io Link Channels

    6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 6.4.3 Configuring the IO Link channels A pre-configuration of the I/O function is automatically used for slot 1 of the subrack. By default, all channels are pre-configured as digital inputs as per the IO-Link specification.
  • Page 35 6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 Deleting the configuration of an IO-Link channel 1. To delete an IO-Link channel, select the desired IO-Link channel in HWConfig. 2. Right click and then select the Clear option in the menu that appears. 3.
  • Page 36 6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 Figure 10: Free IO-Link channel 4. Right click this entry. The following menu appears: Figure 11: Menu dialog 5. Select the Clear option. Press Yes to confirm the dialog that follows. Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 37 6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 Figure 12: Free IO-Link channel Creating an IO-Link channel configuration Click 3x on the + symbols in the hardware catalog of the device you want to configure to reveal a selection of options: Figure 13: IO-Link channel configuration Select the desired option, click and hold down the left mouse button to drag...
  • Page 38 6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 In this mode the channel operates as a digital input. The IO-Link master does not try to establish communication to a connected IO-Link device. SIO mode (DI) This mode is used to parameterize the IO-Link devices.
  • Page 39: Parameterization Of The Io Link Channels

    6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 modules with data lengths of 1-32 input and/or output bytes are available. If no suitable configuration module is available for the device, the next larger data length must be selected.
  • Page 40 6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 If parameter data of a device were stored previously, these data remain stored without any changes. Download only (master to device) Enables the parameter data download function to the IO-Link device on the master.
  • Page 41 6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 Enables the IO-Link parameter data download and upload function. An upload is performed when an IO-Link device is connected and the master does not have any valid data. This is the case if "Disabled and Cleared"...
  • Page 42 6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 IOL Device Validation The IOL Device Validation (IO-Link Device Identification) lets you check the connected devices for the values set in the control program in order to, e.g., identify correctly connected devices and not start operations with them.
  • Page 43 6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 Replacement of the an IO-Link device of the same type is thus only possible if the serial number is changed in the Engineering Tool at the same time. VendorID The VendorID of the IO-link device used can be entered as a decimal value in the VendorID 1 (high-order byte)
  • Page 44 6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 All bits of the output data with a value of 1 are transmitted to the IO-Link device. Hold Last The last valid output value received by the control unit is continuously and cyclically transmitted to the IO-Link device.
  • Page 45: Parameterization Of The Status/Control Module

    6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 6.4.5 Parameterization of the status/control module Figure 18: Status/Control module The status/control module in slot 1/sub-slot 1 is pre-configured for each LioNP IO-LinkMaster. It consists of 4 bytes of input and 4 bytes of output data for the digital IO/ data, and status and control bits of the IO-Link Master.
  • Page 46 6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 The Digital-IO Bit Mapping Mode parameter can be used to define the mappings of the input/output bits that are transmitted in the cyclical data of the Status/Control Module from the control unit to the devices, or from the device to the control unit.
  • Page 47 6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 Diagnostics or diagnostics levels can be enabled or disabled in the General Diagnosis Settings folder. The figure shows the default setting. Attention: "Report U supply voltage fault" is disabled in the default setting, to avoid diagnostic messages due to switching the supply voltage on or off later on.
  • Page 48: Surveillance Timeout Configuration (Lion-P 60 Devices)

    6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 6.4.6 Surveillance Timeout Configuration (LioN-P 60 devices) For LioN-P 60 devices, the separate power supply 2L+ (UAux), which is available on type B IO-Link channels (Ch.B / Pin2), ports 5-8, can also be configured as an additional digital output (tab: "Digital-IO mode for Ch.
  • Page 49: Digital Input Logic

    6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 6.4.7 Digital input logic This parameter can be used to configure the logic of channels used as digital inputs. Figure 23: Digital input logic Default setting NO (Normally Open) for all channels NO (Normally Open) A non-damped sensor has an open switching output...
  • Page 50: Digital-Io Mode For Ch. B/Pin

    6.4 Configuration of the LioN-P 6 Starting operation PROFINET I/O modules in STEP 7 6.4.8 Digital-IO mode for Ch. B/Pin 2 Digital-IO mode for Ch. B/Pin 2 (LioN-P 30 devices) The type B IO-Link ports of the LioN-P 30 devices have a fixed configuration. The functionality is shown in the following figure: Figure 24: Digital IO mode (LioN-P 30 devices) Digital-IO mode for Ch.
  • Page 51 6 Starting operation 6.4 Configuration of the LioN-P PROFINET I/O modules in STEP 7 Figure 25: Digital IO mode (LioN-P 60 devices) Default setting Auxiliary Power Supply (IO-Link Type B) Auxiliary Power (IO-Link Type B) In this mode, Pin 2 and Pin 5 of the type B IO-Link ports, ports 5 - 8, act as an auxiliary voltage output.
  • Page 52: Io-Link Device Parameterization

    6.5 IO-Link Device Parameterization 6 Starting operation 6.5 IO-Link Device Parameterization 6.5.1 SIEMENS IO-Link library The SIEMENS STEP 7 "IO_LINK_CALL" function module can both acyclically write device parameters of an IO-link device and read parameters, measured values and diagnostic data. In a revised version of this library, "IO_LINK_CALL"...
  • Page 53 6 Starting operation 6.5 IO-Link Device Parameterization Figure 27: STEP 7 V5.5 Service data are uniquely addressed via the index and the sub-index and can be accessed or written via the logical start address of the status/control module (ID) inputs, the client access point (CAP = 255) and the corresponding IO-link port (PORT).
  • Page 54: Snmp

    6.6 SNMP 6 Starting operation 6.6 SNMP The PROFINET IO-Link Master devices support required objects required by the PROFINET specification as per protocol standard SNMP v1. These include objects from RFC 1213 MIB-II (System Group and Interfaces Group) and the LLDP MIB. Passwords: Read Community: public Write Community: private...
  • Page 55: Media Redundancy Protocol (Mrp)

    6 Starting operation 6.7 Media Redundancy Protocol (MRP) 6.7 Media Redundancy Protocol (MRP) Redundant PROFINET communication can be implemented with the LioN-P modules via a ring topology without the use of additional switches. A MRP redundancy manager terminates the ring, detects individual failures, and transmits the data packets on the redundant path in case of error.
  • Page 56 6.7 Media Redundancy Protocol 6 Starting operation (MRP) Figure 28: Example of setting up the MRP redundancy manager in STEP7 Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 57 6 Starting operation 6.7 Media Redundancy Protocol (MRP) Figure 29: Example of setting up an MRP redundancy client in STEP7 Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 58: Identification & Maintenance Functions (I&M)

    6.8 Identification & maintenance 6 Starting operation functions (I&M) Figure 30: Example of setting up the response monitoring times in STEP7 6.8 Identification & maintenance functions (I&M) The PROFINET module has the ability to uniquely identify the devices installed in the system via an electronic nameplate. This device-specific data can be read acyclically by the user at any time.
  • Page 59: Supported I&M Features

    0. The specified index is used for mapping the data sets. Data object Length Access Default value / Description [byte] MANUFACTURER_ID Read 0x016A (Belden Deutschland GmbH) ORDER_ID Read Order number of module in ASCII SERIAL_NUMBER Read Defined in production process in ASCII...
  • Page 60 6.8 Identification & maintenance 6 Starting operation functions (I&M) Data object Length Access Default value / Description [byte] INSTALLATION_DATE Read/ 0x20 ff. (empty); Supported data format is a Write visible string with a fix length of 16 byte; “YYYY-MM-DD hh:mm” or “YYYY-MM-DD”...
  • Page 61 6 Starting operation 6.8 Identification & maintenance functions (I&M) Data object Length Access Default value / Description [byte] MANUFACTURER_ID Read 0x016A (Belden Deutschland GmbH) ORDER_ID Read Order number of module in ASCII SERIAL_NUMBER Read Defined in production process in ASCII HARDWARE_REVISION Read...
  • Page 62: Reading And Writing I&M Data

    6.8 Identification & maintenance 6 Starting operation functions (I&M) Data object Length Access Default value / Description [byte] NDEX_CAP1 Read 0xFF (Client Access Point for IOL_CALL) Table 14: I&M 99 (Slot 1, Index 0xB063) IO-Link Device I&M functions The IO-Link device-specific I&M functions 16 and 23 can be read via slot 1, sub-slot 1.
  • Page 63 6 Starting operation 6.8 Identification & maintenance functions (I&M) Data object Length [byte] Data type Coding Description BlockType Word I&M 0: 0x0020 BlockHeader I&M 1: 0x0021 I&M 2: 0x0022 I&M 3: 0x0023 I&M 4: 0x0024 I&M 16 ... 23: 0x0F00 I&M 99: 0x0F00 BlockLength Word...
  • Page 64 6.8 Identification & maintenance 6 Starting operation functions (I&M) Figure 31: Example of a completed I&M 0 read action I&M Write Record I&M data can be written via the standard WRREC (SFB53) function block in STEP 7. The logical address of the slot/sub-slot (ID), the I&M index (INDEX) and the data length (LEN) must be used as handover parameters.
  • Page 65 6 Starting operation 6.8 Identification & maintenance functions (I&M) Figure 32: Example of a completed I&M 1 write action Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 66: Fast Start-Up (Fsu) / Prioritized Start-Up

    6.9 Fast Start-Up (FSU) / Prioritized 6 Starting operation Start-Up 6.9 Fast Start-Up (FSU) / Prioritized Start-Up The LioN-P modules with Fast Start-Up (FSU) support an optimized system start-up. This guarantees a faster restart after the power supply is restored. Fast Start-Up can be activated for the LioN-P modules with PROFINET interface [X1] >...
  • Page 67: Bit Assignment

    7 Bit assignment 7.1 Process data Status and Control module, slot 1/sub-slot 1 7 Bit assignment The LioN-P PROFINET IO-Link masters use a modular device model. Slot 1 subslot 1 contains the IO-Link master status and control module. This module always has 4 bytes of input data and 4 bytes of output data;...
  • Page 68 7.1 Process data Status and Control 7 Bit assignment module, slot 1/sub-slot 1 Port Channel Table 19: Byte 2, IOL-COM state Port Channel Table 20: Byte 3, IOL PD valid Key: The digital input data return the status of the digital inputs. The data in the cells highlighted in blue are only available for LioN-P 60 devices are representing the output status.
  • Page 69 7 Bit assignment 7.1 Process data Status and Control module, slot 1/sub-slot 1 Output data of the Status/Control modules (except 0980 ESL 3x8-121) Port Channel Table 21: Byte 0, Digital Output State Port Channel Table 22: Byte 1, Digital Output State Port Channel Table 23: Byte 2, COM mode...
  • Page 70 7.1 Process data Status and Control 7 Bit assignment module, slot 1/sub-slot 1 Port Channel Table 24: Byte 3, reserved Key: The data in the cells highlighted in blue are only available for LioN-P 60 devices. Byte 0 (Pin 4, C/Q mode): The digital output on the corresponding port can be controlled via the process data.
  • Page 71 7 Bit assignment 7.1 Process data Status and Control module, slot 1/sub-slot 1 Output data of the Status/Control modules for 0980 ESL 3x8-121 Port Channel Table 25: Byte 0, Digital Output State Port Channel Table 26: Byte 1, Digital Output State Port Channel Table 27: Byte 2, COM mode...
  • Page 72: Digital Io Mapping Mode 2 (E2C Compatibility)

    7.1 Process data Status and Control 7 Bit assignment module, slot 1/sub-slot 1 Port Channel Table 28: Byte 3, reserved Key: Byte 0 (Pin 4, C/Q mode): The digital output on the corresponding port can be controlled via the process data. The I/O link port must be configured as a digital output in the Engineering Tool.
  • Page 73 7 Bit assignment 7.1 Process data Status and Control module, slot 1/sub-slot 1 Port Channel Table 30: Byte 1, Digital Input Status Port Channel Table 31: Byte 2, IOL-COM state Port Channel Table 32: Byte 3, IOL PD valid Key: The digital input data return the status of the digital inputs.
  • Page 74 7.1 Process data Status and Control 7 Bit assignment module, slot 1/sub-slot 1 Output data of the Status/Control modules (except 0980 ESL 3x8-121) Port Channel Table 33: Byte 0, Digital Output State Port Channel Table 34: Byte 1, Digital Output Status Port Channel Table 35: Byte 2, COM mode...
  • Page 75 7 Bit assignment 7.1 Process data Status and Control module, slot 1/sub-slot 1 Port Channel Table 36: Byte 3, reserved Key: The data in the cells highlighted in blue are only available for LioN-P 60 devices. Byte 0 (Pin 4, C/Q mode): The digital output on the corresponding port can be controlled via the process data.
  • Page 76 7.1 Process data Status and Control 7 Bit assignment module, slot 1/sub-slot 1 Output data of the Status/Control modules for 0980 ESL 3x8-121 Port Channel Table 37: Byte 0, Digital Output Status Port Channel Table 38: Byte 1, Digital Output Status Port Channel Table 39: Byte 2, COM mode...
  • Page 77: Process Data Io-Link Ports, Slot 1/Sub-Slot 2 - Sub-Slot

    7 Bit assignment 7.2 Process data IO-Link ports, slot 1/ sub-slot 2 - sub-slot 9 Port Channel Table 40: Byte 3, reserved Key: Byte 0 (Pin 4, C/Q mode): The digital output on the corresponding port can be controlled via the process data. The I/O link port must be configured in digital output mode.
  • Page 78: Diagnostics Processing

    8.1 Error in the system/sensor power 8 Diagnostics processing supply 8 Diagnostics processing 8.1 Error in the system/sensor power supply The voltage value for the incoming system/sensor power supply is also monitored globally. If the voltage drops below approx. 18 V, or exceeds approx.
  • Page 79: Overload/Short-Circuit Of The Io Port Sensor Supply Outputs

    8 Diagnostics processing 8.3 Overload/short-circuit of the IO port sensor supply outputs diagnostic messaging is disabled by default and must be enabled via parameterization. The following group diagnostic message is generated: Channel number of diagnosis 0x8000 (diagnosis not channel-specific) Channel related diagnosis code 0x0103 Channel related diagnosis code message Undervoltage...
  • Page 80: Overload/Short Circuit Of The Digital 500 Ma Outputs

    8.4 Overload/short circuit of the digital 8 Diagnostics processing 500 mA outputs Alternatively, the following error message is generated: Channel number of diagnosis 0x01 - 0x08 Channel related diagnosis 0x0113 code Channel related diagnosis High temperature limit of IO-Link port driver exceeded (short circuit or code message overload), detected by IO-Link master 8.4 Overload/short circuit of the digital 500 mA...
  • Page 81 8 Diagnostics processing 8.5 Overload/short circuit of the digital outputs Target value Actual value Comment Active Active OK, no diagnosis OK, no diagnosis Active Short-circuit Channel indicator is red. Channel error bit in the diagnosis is set. Channel is locked after the error is rectified. Table 41: Interpretation of channel errors When an output channel is activated (rising edge of the channel state) or deactivated (falling edge), the channel errors are filtered for the period that...
  • Page 82: Overload/Short Circuit Of The Type B Port Aux. Power Supply

    8.6 Overload/short circuit of the Type 8 Diagnostics processing B port aux. power supply 8.6 Overload/short circuit of the Type B port aux. power supply 8.6.1 For LioN-P 30 devices In case of an overload or a short circuit between pin 2 and pin 5 on these ports (X5 - X8), the following group diagnostic message (non channelspecific) is generated: Channel number of diagnosis...
  • Page 83: Io-Link Device Diagnostics

    8 Diagnostics processing 8.8 IO-Link Device Diagnostics Channel number of diagnosis 0x01 - 0x08 Channel related diagnosis 0x0006 code Channel related diagnosis Line break code message Extended description Missing/wrong device, broken wire or short circuit/overload at Pin 4/ Ch. A of IOL-Port, detected by IO-Link Master. 8.8 IO-Link Device Diagnostics Diagnoses of IO-Link devices that the device sends to the IO-Link Master are reported through a standard channel diagnosis and an extended channel...
  • Page 84 8.8 IO-Link Device Diagnostics 8 Diagnostics processing 1-8 of the IO-Link Master port whose connected device is reporting an error. Mode Type Res. Instance Table 42: Event Qualifier Value Definition Unknown Application 5 ... 7 reserved Table 43: Event Qualifier Instance Event Qualifier Res.
  • Page 85 8 Diagnostics processing 8.8 IO-Link Device Diagnostics Value Definition Reserved Information Warning Error Table 44: Event Qualifier Type Value Definition Reserved Event single shot Event disappears Event appears Table 45: Event Qualifier Mode Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 86: Port Configuration Tool

    The key technological element for the operation of the connected devices is the mandatory IODD (IO Device Description) file. The IODD is accepted worldwide. The Belden IO-Link Device Tool supports IO-Link V1.0 (IODDs V1.0.1) and IO-Link V1.1 (IODDs V1.1). Main functions:...
  • Page 87 9 Port Configuration Tool Figure 33: Port configuration tool - Main window Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 88: The Integrated Web Server

    10 The integrated web server 10 The integrated web server The LioN-P modules are equipped with an integrated web server which makes functions available for the configuration of modules and display of status and diagnostic information. Enter http:// followed by the IP address, such as http://192.168.1.5, in your web browser’s address bar.
  • Page 89: The Status Page

    10 The integrated web server 10.1 The Status page 10.1 The Status page The status page provides a quick overview of the current state of the module. The left side shows a graphical representation of the module with all its LEDs and the positions of the rotary encoding switches.
  • Page 90 10.1 The Status page 10 The integrated web server Forcemode The Forcemode is a test option for the plant engineer, the input and output data can be set from this web page. The physical input data and the logical output data from the controller can be overruled in this mode.
  • Page 91 10 The integrated web server 10.1 The Status page Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 92: The Ports Page

    10.2 The Ports page 10 The integrated web server 10.2 The Ports page Detailed port information is shown here. Port Diagnosis shows incoming and outgoing diagnoses in clear text. Pin 2 and Pin 4 contain information about the configuration and state of the port. For IO-link ports, additional information relating to the connected sensor and the process data is displayed.
  • Page 93: The System Page

    10 The integrated web server 10.3 The System page 10.3 The System page The System page shows basic information for the module. The current firmware, its version, and the firmware date can be viewed below Firmware as well as the version of the web interface. All the information about the module itself is located below Device.
  • Page 94 10.3 The System page 10 The integrated web server Attention: During the factory reset process the BF/MS/RUN LED is cyclic triple flashing red. After completion the factory reset the BF/MS/ RUN LED is cyclic triple flashing green. Afterwards perform a power cycle and wait 10 seconds.
  • Page 95: The User Page

    10 The integrated web server 10.4 The User page 10.4 The User page The User page provides the user management of the web interface. New users with access rights Admin or Write can be added here. For security reasons please change the default admin password immediatlely after configuring the device.
  • Page 96: Technical Data

    11.1 General 11 Technical data 11 Technical data 11.1 General Protection class IP65 IP67 IP69K (This only applies if the connectors are screwed together or covers are used.) (not under U investigation) Ambient temperature -20° C to +70° C (- 4° F to +158° F) (Operation) Weight LioN-P 30...
  • Page 97: Profinet Protocol

    11 Technical data 11.2 PROFINET protocol 11.2 PROFINET protocol Protocol PROFINET IO Device V2.3 Conformance Class C (CC-C) Netload Class Update cycle 1 ms GSDML file GDSML-V2.3x-LumbergAutomation-LioN-Pyyyymmdd.xml Transmission rate 100 Mbit/s, full duplex Transmission procedure 100BASE-TX Autonegotiation is supported Vendor ID Device ID 0305 (same for all LioN-P modules) Supported Ethernet protocols...
  • Page 98: Power Supply For The Module Electronics/Sensors

    11.3 Power supply for the module 11 Technical data electronics/sensors 11.3 Power supply for the module electronics/ sensors Nominal voltage U 24 V DC (SELV/PELV) Voltage range 18-30 V DC Power consumption of module electronics Typically 160 mA (+/- 20 % at U rated) Voltage level of the sensor power supply Min.
  • Page 99: Power Supply Type B Ports (Auxiliary Supply)

    11 Technical data 11.4 Power supply type B ports (auxiliary supply) 11.4 Power supply type B ports (auxiliary supply) Nominal voltage U 24 V DC (SELV/PELV) Voltage range 18-30 V DC Reverse polarity protection Operational indicator (U LED green, U > 18 V +/- 1 V or U <...
  • Page 100: Configured As A Digital Input

    11.5 IO-Link Master Ports (X1 - X8, 11 Technical data Ch. A/C/Q/ Pin 4) 11.5.1 Configured as a digital input Input connection Type 1 as per IEC 61131-2 Nominal input voltage 24 V DC Input current Typically 3 mA Channel type Normally open, p-switching Number of digital inputs Status indicator Yellow LED...
  • Page 101: Configured As An Io-Link Port In Com Mode

    11 Technical data 11.6 Digital inputs (X1 – X4, type A ports, ch. B/pin 2) 11.5.3 Configured as an IO-Link port in COM mode IO-Link Master v1.1, IEC 61131-9 specification Communication rates 4.8 kbaud (COM 1), 38.4 kbaud (COM 2) and 230.4 kbaud (COM 3) Line lengths in the IO- max.
  • Page 102 11.6 Digital inputs (X1 – X4, type A 11 Technical data ports, ch. B/pin 2) Figure 34: Block diagram Class-A Port Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 103: Lion-P 60: U Aux

    11 Technical data 11.7 LioN-P 60: U config. as a digital output (X5 - X8, type B ports, ch. B/pin 2) 11.7 LioN-P 60: U config. as a digital output (X5 - X8, type B ports, ch. B/pin 2) Output type Normally open, p-switching Nominal output current per channel 2 A (for U...
  • Page 104: Lion-P 30: U Aux (X5 - X8)

    11.8 LioN-P 30: U (X5 - X8) 11 Technical data 11.8 LioN-P 30: U (X5 - X8) Nominal output current per module max. 4 A Nominal output current per port max. 4 A Short-circuit/overload protected yes/yes Status indicator LED white per output Diagnosis indicator Red LED per channel Table 56: LioN-P 30 extended sensor supply (X5 - X8) type B ports...
  • Page 105: Differences Between 0980 Esl 3X8-121 And 0980 Esl 3X9-121

    11 Technical data 11.9 Differences between 0980 ESL 3x8-121 and 0980 ESL 3x9-121 Figure 36: Bock diagram Class-B Port, variant 0980 ESL xx8-xxx Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 106: Leds

    11.10 LEDs 11 Technical data 11.10 LEDs Green 18 V +/-1 V < Auxiliary sensor/actuator voltage < 30 V +/-1 V Auxiliary sensor/actuator voltage < 18 V +/-1 V or Auxiliary sensor/actuator voltage > 30 V +/-1 V * if "Report U supply voltage fault" is enabled. None of the above conditions Green 18 V +/-1 V <...
  • Page 107 11 Technical data 11.10 LEDs PROFINET diagnostic alarm active Watchdog time-out; fail safe mode is active flashing at 1 Hz DCP signal service is initiated via the bus flashing at 2 Hz, 3 sec Red double Firmware update flash None of the above conditions Table 57: Information on the LED colors Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...
  • Page 108: Accessories

    12 Accessories 12 Accessories In order to get access to various types of accessories, please visit our web page: http://www.beldensolutions.com Manual LioN-P PROFINET IO-Link Master Version 2.1 10/2017...