Content Content About this manual General information Explanation of symbols 1.2.1 Use of danger information 1.2.2 Use of general information Version information Safety instructions Intended use Qualified personnel System description Product overview 3.1.1 Module variants 3.1.2 Accessories Assembly and wiring General information Outer dimensions 4.2.1 Module 0980 ESL 803...
Page 4
Content 5.4.1 Assigning a unique device name 5.4.2 Assigning a device name to a LioN-R module 5.4.3 Device replacement without removable media/PD 5.4.4 The parameter settings of the LioN-R modules 5.4.5 Prioritized startup 5.4.6 Resetting the LioN-R modules to factory settings Media Redundancy Protocol (MRP) Assignment of the process data 16DI modules:...
Page 5
Content Alarm and error messages of LioN-P/-R modules via PROFINET 7.7.1 Alarm evaluation in STEP 7 7.7.2 Structure of diagnostic data records The integrated web server The Home page The Configuration page (Config) The Status page The Contact page Reading the process and diagnostic data Technical data General Bus system...
Fax +49 (0) 23 55 / 5044-333 support-automation@belden.com www.lumberg-automation.com Belden Deutschland GmbH – Lumberg Automation™ – reserves the right to make technical changes or changes to this manual at any time without notice. Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
About this manual 1.2 Explanation of symbols Explanation of symbols 1.2.1 Use of danger information Danger information is denoted as follows: DANGER Means that death, serious physical injury or substantial damage to property will occur if the required safety measures are not taken. WARNING Means that death, serious physical injury or substantial damage to property can occur if the required safety measures are not taken.
About this manual 1.3 Version information Version information Index Created Changed Changed Version number Version 1.0 Version 1.1 Version 1.2 Date May 2013 December 2015 February 2016 Name/department Knipp/PM Knipp/PM Lieb/R&D Table 1: Overview of manual revisions Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
Page 10
About this manual 1.3 Version information Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
Safety instructions 2.1 Intended use Safety instructions Intended use The devices described in this manual are decentralized input/output assemblies on a PROFINET IO network. We adhere to all safety standards when developing, producing, testing, and documenting our products. When you adhere to the handling specifications and safety instructions described for the configuration, assembly, and correct operation, there should not normally be any risks for people or equipment.
Only Belden Deutschland GmbH – Lumberg Automation™ – is permitted to make changes to the hardware or software of the products that go beyond the scope of this manual.
System description System description The LioN (Lumberg I/O network) -P and -R module series includes standalone fieldbus devices for decentralized use in harsh industrial environments. The devices feature easy handling of I/O data in a higher-level bus system. They are especially suitable for use in machines and installations with a moderate I/O concentration over separate assemblies.
System description 3.1 Product overview For the functions of the rotary encoding switches with multiprotocol, refer to the Multiprotocol Manual. Product overview 3.1.1 Module variants Item number Description I/O ports Design LioN-R 16 DI/ LioN-P 16 DI 0980 ESL 801-PNET 16DI-M12-R Decentralized I/O 8 x M12 Sturdy/metal...
System description 3.1 Product overview 3.1.2 Accessories Item number Description 0985 342 100/… M Connection cable for PROFINET, assembled on both sides with M12 connectors, straight, 4-pin, D-coded 0985 342 102/… M Connection cable for PROFINET, assembled on both sides with an M12 connector, straight, 4-pin, D-coded 0985 342 104/…...
Page 16
System description 3.1 Product overview Item number Description 0985 706 100/… M Connection cable for PROFINET, with M12 connector at both ends, straight, 4-pin, D-coded, 24AWG TPE with blue-green casing, highly flexible, multi-wire/unshielded, 2 twisted wire pairs. 0985 706 101/… M Connection cable for PROFINET, crossover, with M12 connector at both ends, straight, 4-pin, D-coded, 24AWG TPE with blue-green casing, highly flexible, multi-wire/unshielded, 2 twisted wire pairs.
Assembly and wiring 4.1 General information Assembly and wiring General information Mount the module with 2 screws (M6x25 / 30) for LioN-R and 2 screws (M4x25/30) for LioN-P on a level surface. The torque required here is 1 Nm. Use washers for all fastening methods as per DIN 125. For the mounting holes, use a distance of 237.3 to 239.7 mm for the LioN-R modules, a distance of 190.3 to 191.8 mm for LioN-P modules with 7/8"...
Page 18
Assembly and wiring 4.1 General information Note For UL application: Be sure to use a UL-certified cable with a suitable evaluation to connect the devices (CYJV or PVVA). To program the control, please refer to the OEM information, and only use suitable accessories. Note For UL application:...
Assembly and wiring 4.3 Port assignments Port assignments All the contact arrangements shown in this chapter show the frontal view of the connection area for the connectors. 4.3.1 PROFINET ports, M12 socket, 4-pin, D-coded Color coding: green Figure 1: Schematic drawing, ports X01, X02 Port Signal Function...
Page 23
Assembly and wiring 4.3 Port assignments Figure 3: Schematic drawing, port X04 (OUT) Port Signal Function 0980 ESL 801 0980 ESL 802 0980 ESL 803 Power supply *see note Actuator GND (0V) X03, X04 GND (0V) System/sensors GND (0V) Ground Functional ground +24 V System/sensors...
Assembly and wiring 4.3 Port assignments 4.3.3 Power supply with M12 power L-coded Color coding: gray Figure 4: Schematic diagram of the M12 L-coding (connector), port X03 (IN) Figure 5: Schematic diagram of the M12 L-coding (socket), port X04 (OUT) Power supply Signal Function...
Assembly and wiring 4.3 Port assignments 4.3.4 Ports for the sensors/actuators Design: M12 socket, 5-pin Color coding: black Figure 6: Schematic drawing, ports X1 to X8 Port Function 16DI 16DO 8DI/8DO Sensor/actuator 1 +24 V DC n.c. +24 V DC (ports X1..X4) n.c.
Page 26
Assembly and wiring 4.3 Port assignments Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
Configuration and startup 5.1 GSDML file Configuration and startup The configuration and startup of LioN-P/-R PROFINET modules described on the following pages was carried out using the STEP 7 software of Siemens AG. If you are using a control system from another control system provider, please consult the associated documentation.
Configuration and startup 5.3 SNMP SNMP The modules support the Ethernet network protocol SNMP (Simple Network Management Protocol). The network management information is displayed according to MIB-II (Management Information Base), which is defined in RFC 1213. Configuration of the LioN-R PROFINET I/O modules in STEP 7 After installation of the GSDML files for the LioN-R PROFINET modules, they are available in the hardware catalog at...
Configuration and startup 5.4 Configuration of the LioN-R PROFINET I/O modules in STEP 7 5.4.1 Assigning a unique device name PROFINET I/O devices are addressed on PROFINET via a unique device name. This can be freely assigned by the user, but may only be used once on the network.
Configuration and startup 5.4 Configuration of the LioN-R PROFINET I/O modules in STEP 7 5.4.2 Assigning a device name to a LioN-R module An online PROFINET connection between the programming device and the module is required to assign the device name to a module. Select the LioN-R module and open the Target device >...
Configuration and startup 5.4 Configuration of the LioN-R PROFINET I/O modules in STEP 7 5.4.3 Device replacement without removable media/PD PROFINET I/O devices that support the function of device replacement without removable media or PD can be replaced by the same devices in an existing PROFINET network without having to use removable media or a programming device.
Configuration and startup 5.4 Configuration of the LioN-R PROFINET I/O modules in STEP 7 NOTE The replacement device must be in the state on delivery (factory settings) for replacement without removable media/PD. If necessary, the factory settings must be restored. 5.4.4 The parameter settings of the LioN-R modules You get to the parameter settings via the menu item...
Page 33
Configuration and startup 5.4 Configuration of the LioN-R PROFINET I/O modules in STEP 7 The Report Alarms parameter With this parameter, you enable or disable the alarms of the device- specific diagnostics via PROFINET. The setting is available for all three different types of modules (16DI, 16DO, 8DI/8DO).
Configuration and startup 5.4 Configuration of the LioN-R PROFINET I/O modules in STEP 7 The Surveillance Timeout parameter This parameter is provided by the module types with digital outputs (16DO, 8DI/DO). The firmware of the modules allows you to define a delay time before the monitoring of the output currents begins, known as the surveillance timeout.
Configuration and startup 5.5 Media Redundancy Protocol (MRP) 5.4.6 Resetting the LioN-R modules to factory settings The LioN-P /-R modules are reset to the factory settings in Step 7 via the menu item . After you search Target device > Edit accessible devices through the subscribers accessible online and select the LioN-P/-R module, this module is reset to the factory settings by clicking the "Reset to factory settings"...
Page 36
Configuration and startup 5.5 Media Redundancy Protocol (MRP) A max. of 50 devices are permissible in the ring. All devices share the same redundancy domain. One device must be configured as the redundancy manager. All other devices must be configured as redundancy clients. ...
Page 37
Configuration and startup 5.5 Media Redundancy Protocol (MRP) Example of setting up the response monitoring times in STEP7: Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
Page 38
Configuration and startup 5.5 Media Redundancy Protocol (MRP) Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
Assignment of the process data 6.1 16DI modules: - 0980 ESL 801- PNET 16DI-M12-R - 0980 ESL 301- Assignment of the process data This chapter describes the assignment of the process data of the controller to the I/O channels of the modules. 16DI modules:...
Assignment of the process data 6.3 8DI/8DO modules: - 0980 ESL 803-PNET 8DI/8DO-M12-R - 0980 Input Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte n Byte n+1 8B The following applies here: ...
Assignment of the process data 6.3 8DI/8DO modules: - 0980 ESL 803-PNET 8DI/8DO-M12-R - 0980 The following applies here: 1A ... 4A: Actual status of input channel A (contact pin 4) of the M12 socket connections 1 to 4. ...
Page 42
Assignment of the process data 6.3 8DI/8DO modules: - 0980 ESL 803-PNET 8DI/8DO-M12-R - 0980 Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
Diagnostic properties of the modules 7.1 Channel error Diagnostic properties of the modules The modules provide advanced diagnosis behavior, in particular for the output channels to determine errors in the transmission. The firmware of the modules distinguishes between 5 different types of error. Channel error A channel error is determined by comparing the target value set by a controller and the actual value of an output channel.
Diagnostic properties of the modules 7.2 Voltage error at the M12 slots (sensor short-circuit) The filter is used to avoid premature error messages when a capacitive load is activated or an inductive load is deactivated, and during other voltage peaks when a status changes. When a channel is in the static state –...
Diagnostic properties of the modules 7.4 Error in the actuator power supply If there is an overload, the status indicator of the active output channel lights up red. If both output channels of an M12 slot are active during an overload, both status indicators light up red.
Diagnostic properties of the modules 7.5 Error in the system/sensor power supply Error in the system/sensor power supply The voltage value for the system/sensor power supply is also monitored globally. If the value goes outside the voltage range of 18 to 30 V, an error message is created.
Diagnostic properties of the modules 7.6 Diagnostic display in the integ- rated web server 7.6.1 16DI modules Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Byte 1 LV-U Byte 2 Table 14: Bit assignment for the 16 DI modules 7.6.2 16DO modules Bit 7...
Diagnostic properties of the modules 7.7 Alarm and error messages of LioN-P/-R modules via PROFINET Alarm and error messages of LioN-P/-R modules via PROFINET Note Alarm and error messages are only transmitted via PROFINET when the parameter for diagnostics is activated in the configuration of the modules in the control system.
Diagnostic properties of the modules 7.7 Alarm and error messages of LioN-P/-R modules via PROFINET 7.7.2 Structure of diagnostic data records For the presentation of the diagnostic data records, the block version 0x0101 and the format identifier (USI, user structure identifier) 0x8000 is used. The data values "ChannelNumber"...
Page 50
Diagnostic properties of the modules 7.7 Alarm and error messages of LioN-P/-R modules via PROFINET Confirming the "Hexadecimal representation" button in the window above opens a view of the diagnostic data record in hexadecimal format, along with its structure. Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
The integrated web server 8.1 The Home page The integrated web server The LioN-P/-R modules are equipped with an integrated web server which makes functions available for the configuration of modules and display of status and diagnostic information. Using a standard web browser, the provided functions can be accessed via an existing TCP/IP connection.
The integrated web server 8.2 The Configuration page (Config) The Configuration page (Config) If you select the "Config" menu item from the menu bar of the Home window, a new window with the configuration options will open. On this page, you can reset the modules to the factory settings. To do this, check the box and confirm by pressing the "Apply"...
The integrated web server 8.3 The Status page Note Please note that if you reset the modules to the factory settings, the PROFINET name and IP address are also reset to the default values. It may not be possible to access the web server of the modules and exchange data in the PROFINET network after the reset.
The integrated web server 8.4 The Contact page The Contact page The address of the contact page is: http://[IP-Adresse]/contact.htm This page provides information on the contact data for Belden Deutschland GmbH. Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
The integrated web server 8.5 Reading the process and diagno- stic data Reading the process and diagnostic data You have the option to read the process and diagnostic data for the LioN-R modules using the integrated web server. The web server provides the data in standardized JSON format.
Page 56
The integrated web server 8.5 Reading the process and diagno- stic data The response has the following object structure: Process data Produced (inputs): Array[a,b] Consumed (outputs): Array[a,b] Diagnostics Diag: Array[a,b,c,d,e] Technical manual LioN-P/ -R PROFINET Release 1.2 02/2016...
Technical data 9.1 General Technical data General Protection class IP 67 (only when the connectors are screwed in or when protective caps are used) Ambient temperature Lion-R (0980 ESL 8xx): -10 °C to +60 °C (+14 °F to +140 °F) Lion-P(0980ESL 3xx):...
Technical data 9.3 Power supply for the module elec- tronics/sensors Supported Ethernet Ping protocols LLDP SNMP (network diagnostics) HTTP TCP/IP Switch functionality Integrated IRT is supported PROFINET interface Connections 2 M12 sockets, 4-pin, D-coded (see pin assignments) Autocrossing is supported Table 18: Information on the bus system Power supply for the module electronics/sensors...
Technical data 9.5 Inputs Delay time of the undervoltage detection < 20 ms Reverse polarity protection Operational indicator (U LED green, 18 V <= U <= 30 V LED red, U < 18 V or U > 30 V Table 20: Information on the power supply for the actuators Note The reverse polarity protection only works if the supply of the actuators is protected within overcurrent fuse (10 A, mT) and switched off upon short-...
Technical data 9.6 Outputs Outputs Output connection Type 1.6 A as per IEC 61131-2 (LioN-R) Type 2.0 A as per IEC 61131-2 (LioN-P) Nominal output current per channel: 1.6 A, see info 1 (LioN-R) 2.0 A (LioN-P) Signal status “1” max.
Technical data 9.7 LEDs LEDs Green System/sensor power supply, voltage level 18 V <= U <=30 V System/sensor power supply, voltage level 18 V <= U <=30 V No system/sensor power supply Green Actuator power supply, voltage level 18 V <= U <= 30 V Actuator power supply, voltage level U <...