SureCross DX99 FlexPower Node (Metal Housing)
Analog Configuration, Switch 2 OFF
Descriptions
Sample/Report Rate 15 minutes
Sample/Report Rate 30 minutes
Modbus or UCT configured (overrides DIP switches)
Analog IN 2, Discrete 1, and Discrete 2 are not powered from switched power terminals. In this configuration, SP2 is
disabled. If you need SP2, contact the factory.
* Default positions
Discrete Input Type
Select the type of discrete input sensors to use with this device: sourcing (PNP) sensors or sinking (NPN) sensors.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus
command. All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the
parameters listed in the table.
Sample and Report Rates
The sample interval, or rate, defines how often the SureCross device samples the input. For battery-powered applications,
setting a slower rate extends the battery life.
The report rate defines how often the Node communicates the I/O status to the Gateway. Change of state reporting sets
the system to report only when the value crosses the threshold setting. For FlexPower
rate to a slower rate extends the battery life.
Warm-Up Time
The warm-up time defines how long the device must power up the sensor before a stable sensor reading is taken.
Terminal Blocks and Wiring
For CSA C/US and LCIE/ATEX approved wiring procedures and to check the Entity Parameters (Safety Parameters), refer
to the complete control drawing, document
The GND connection can be considered the same as the housing ground when using a stainless steel antenna feedthrough
(model BWA-HW-016 or BWA-HW-017).
When the stainless steel antenna feedthroughs are not used, the GND connection is isolated from the metal housing.
BAT
GND
SP2
SP1
GND
DI2
GND
DI1
SP2
AI2
GND
SP1
AI1
GND
LED Behavior for the Nodes
Nodes do not sample inputs until they are communicating with the Gateway. The radios and antennas must be a minimum
distance apart to function properly. Recommended minimum distances are:
P/N 142497 Rev. L
3
141513
at www.bannerengineering.com.
Ax+ and Ax–. Analog IN x. Analog inputs for devices requiring more
than one connection, such as thermocouples or RTDs. When there is
no Ax–, use Ax+ as an analog input.
DIx. Discrete IN x
GND. Ground/dc common connection
SPx. Switch Power; provides variable power sources for external
devices