Download Print this page

Banner DX99N9X1S2N0M2X0D2 Manual page 3

Surecross dx99 flex power node (metal housing)

Advertisement

SureCross DX99 FlexPower Node (Metal Housing)
DIP Switch Settings
Device Settings
Rotary dial address mode
Extended address mode
Analog Configuration
Discrete Configuration
* Default configuration
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended
addressing. In rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the
device ID. The wireless network is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and
receive information from the Gateway to which they are bound. In extended address mode, wireless networks may contain
up to 48 radio devices. For more information on extended address mode, refer to the SureCross
product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address
mode, change the DIP switch to the ON position.
Analog or Discrete Configuration
Select between an analog configuration or a discrete configuration using the DIP switch specified in the table. The default
switch settings for this device are all in the OFF position.
Analog Configuration - Switch 2 OFF (10V Boost Models)
For analog configuration, DIP switch 2 is in the OFF position (factory default). Analog configuration has analog IN 1 linked
to switch power 1 (SP1) and is programmable using switches four through eight. Sample and report rates for analog input
2 are listed in the specifications. Discrete inputs 1 and 2 are also active in this configuration and the input types are
defined using switch 3.
Analog Configuration, Switch 2 OFF
Descriptions
Discrete Input Sinking (NPN)
Discrete Input Sourcing (PNP)
Warm-up Time 10 milliseconds
Warm-up Time 62.5 milliseconds
Warm-up Time 125 milliseconds
Warm-up Time 2 seconds
Sample/Report Rate 1 second
Sample/Report Rate 2 seconds
Sample/Report Rate 4 seconds
Sample/Report Rate 16 seconds
Sample/Report Rate 64 seconds
Sample/Report Rate 5 minutes
Sample/Report Rate 15 minutes
Modbus or UCT configured (overrides DIP switches)
P/N 142497 Rev. L
3
OFF*
ON
www.bannerengineering.com - Tel: +1-763-544-3164
1
OFF*
ON
DIP Switches
4
5
OFF*
OFF*
OFF
ON
ON
OFF
ON
ON
OFF*
OFF
OFF
OFF
ON
ON
ON
ON
Switches
2
OFF*
ON
Wireless I/O Network
6
7
8
OFF*
OFF*
OFF
ON
ON
OFF
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
ON