In order to fulfill the local requirements, the programmable user functions may be
adjusted by the single programming steps.
1
2
1
2
3
4
7
Procedure to enter programming mode / Access Level 3
1. Set system to state non-alarm and provide operating access level 2 (see
Operating access, chapter 6.1.1)
2. Hold key (3) and press numeric keys (7) 1, 4, 2, 4, 2, 3, 2, 1 one after the other
Continuous top-down flash up of LED block (1); indicates mode programming
Procedure to exit programming mode
1. Press numeric keys (7) 1 and 4 simultaneously
automatic timeout if no further key is pressed for more than 4 min.; LED block
(1) stops flashing
Poll checksum (without display module)
In order to find out whether the user functions have been changed since the last
visit of the service engineer.
1. Set system to mode programming (LED 1 = on)
2. Press numeric keys (7) 2 and 3 simultaneously
3. Read out LED sequence (4) within 10 sec. (only possible once within program-
ming sequence)
LED 1 and 8 are flashing slowly; indicating state checksum
4. write sequence of LED 2 to 7 into the checksum list
Note:
Control unit with an equipped display module
see Poll service informations
3
4
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
5
6
1
2
3
4
9 9 9 9
9 9 9 9
8
8
A6V10265083_a_en_--
03.2010