Trouble Shooting; Interpretation Of Fault Led Flashing - Siemens FC1008-A Technical Specification

Fire control unit
Table of Contents

Advertisement

Trouble shooting

10
Trouble shooting
10.1

Interpretation of fault LED flashing

Indicator
LED 2
Fault
flashing fast
LED 10
Earth fault
Flashing fast
LED 11
Power fault
flashing fast
flashing slow
LED 12
System fault
flashing fast
LED 13
Alarm horn fault
flashing fast
LED 14
Fire controls fault
flashing fast
LED 15
RT-Fault
flashing fast
LED 23
RT-Alarm
flashing fast
LED zone x
Yellow zone LED
flashing fast
Display
Indicates 88.88
44
Building Technologies
Fire Safety & Security Products
LED
1
2
3
4
5
6
3
1
2
4
Cause / Action to be taken
There is a fault in the system
check if there is another fault LED flashing, if not
check if control input Fault is activated
Any part of the system has a leakage to earth
Remove one external line (detector line etc.) after the other until the fault disappears, then repair
the defective line
if no external line has a leakage to earth replace mainboard
Battery is disconnected or low
Replace battery
Mains supply is missing (after delay has expired)
Check internal fuse or external mains breaker
The microcomputer has failed (system not working)
Switch power off and restart, if fault continues replace mainboard
There is a fault in the monitored control lines (horn)
Check lines for a short circuit or break or missing/defective EOL
If control card FCA1003 is used, check LEDs DL1 - DL4 to define faulty line
There is a fault on a monitored control line (programmed in step 5 to option 12 or 13)
Check line for a short circuit or break or missing/defective EOL
Control input Fault RT is active, or if programmable control input with option 1 is active (Fault re-
mote transmission device)
Check remote transmission device
There is a fault on a monitored control line (programmed in step 5 to option 14)
Check line for a short circuit or break or missing/defective EOL
There is a fault on a monitored control line (programmed in step 5 to option 11)
Check line for a short circuit or break or missing/defective EOL
There is a fault in zone number x
Check whether any detector head is removed
Check line for short circuit or break or missing/defective EOL
Clock not set (with new system start up or after power down)
Set date and time
LED
LED
7
16
8
9
10
11
12
13
14
15
17 (23)
9 9 9 9