Configuration
8.3.6

Step 6, measures against false alarms

8.3.7

Step 7, control lines on alarm

8.3.8

Step 8, special zone parameters

8.3.9

Step 9 not used

8.3.10 Step 10, detector line short or break

36
Building Technologies
Fire Safety & Security Products
Option
Setting
Function: Zone with alarm verification
1
no alarm verification
2
Alarm only if second Alarm within 60 sec.
1st alarm = automatic Reset with short flash up of zone
LED
Function: Zone disabled in mode manned
3
not disabled
4
disabled as long as mode manned is active
Note:
These measures are only justified on severe environmental conditions.
Option
Setting
Function: Zone with not activated control lines on Alarm
1
both control lines activated
2
both control lines not activated
3
control line 1 not activated
4
control line 2 not activated
Option
Setting
Function: Behavior on Alarm immediately after Reset
1
renewed Alarm
2
alarm < 15 sec. after Reset initiates line Fault
Function: Driver output per zone
3
active if zone is on Alarm
remains until Reset
4
active if zone is on Alarm, Fault, Disabled or Test
remains until Reset or state inactive
Option
Setting
Function: Zone state self-hold on Alarm
1
state line short / break = Fault
2
state line short = Alarm 2
state line break = Fault
3
state line break = Alarm 2
state line short = Fault
4
state line short = Alarm 1
state line break = Fault
Key
LED zone 1 - x
Red
yellow
zone 1 – x
Default off
on
zone 1 – x
Default off
on
Key
LED zone 1 - x
Red
yellow
zone 1 - x
Default off
on
on
on
on
Key
LED zone 1 - x
Red
yellow
zone 1 - x
Default off
on
zone 1 - x
Default off
on
Key
LED zone 1 - x
Red
yellow
zone 1 - x
Default off
on
on
on
on
A6V10265083_a_en_--
03.2010