Function and design
Driver outputs
Function / Application
Mode manned
active if system is in mode manned
Alarm 1
active on Alarm 0 and 1 (inactive on Alarm 2)
blocked with controls disabled
Alarm 2
active on Alarm 2 until Reset
blocked with controls disabled
Disable
active if any part of the system is disabled
Fault
active on Fault until restored
Alarm 1/2
active on Alarm 0, 1 and Alarm 2 until Reset
blocked with controls disabled
Zone 1 - 8
Active on zone alarm, or zone fault, switched off or test
blocked with controls disabled
see Step 8, special zone parameters
5.1.2
Power supply
5.1.3
Line bridging at removed detector head
16
Building Technologies
Fire Safety & Security Products
N
Mains 230 VAC
L
3.15 AT
If a detector head is removed from a detector line, the control unit signal a fault,
while the manual call point is still able to set off an alarm (support diode
bases BS5839Pt1)
removed detector heads
+
Detector line
_
Schottky diode
Achieved with
line card FCA1007-B (factory equipped)
resistor EOL FCE1003-B (included in panel accessories) and Z-diode
special detector base (eg. DB1102A, part number 534851) equipped with Schot-
tky diode (1N5819) in parallel to the monitoring jumper inside detector head
Load / rating
Remarks
max. 40 mA/24 V
for internal and external use
–
BDZ1000-B
inserted detector heads
Z-diode
monitoring jumper
in the detector head
Manual call point
+
_
A6V10265083_a_en_--
03.2010