Poll Service Informations; Delete Alarm Counter And Event Memory - Siemens FC1008-A Technical Specification

Fire control unit
Table of Contents

Advertisement

6.2.4

Poll service informations

6.2.5

Delete alarm counter and event memory

1. Start
2. Approve
3. Delete
4. Confirm
5. End
Automatic stop
Building Technologies
Fire Safety & Security Products
The following information can be displayed on the display module:
last change of configuration (date/time and check sum)
last test alarm (date/time and zone number)
version of firmware
Requirement
Queries about service information are only possible if there is no alarm and operat-
ing access on level 2 is given.
Procedure
1. Hold key acknowledge then, enter the password for the corresponding service
information by using the numeric keys.
2. The requested query can be selected with the corresponding numeric keys.
3. To end the query, press key acknowledge. The request will be automatically
stopped if an alarm occurs or if there is no further entry for more than a minute.
Query about the last change of configuration
Entry
Hold key acknowledge and
enter 11114444
1
2
3
4
Query about the last test alarm
Entry
Hold key acknowledge and
enter 33331111
1
2
3
4
Request about the firmware
Entry
Hold key acknowledge and
enter 2211
Common command to delete both alarm counter and event memory.
hold key acknowledge and key in code 3, 3, 2, 2, 1, 4, 4, 3
by using numeric keys
hold key reset and key in code 3, 4, 4, 1, 3, 3, 2, 1 by using
numeric keys
press numeric key 2
press simultaneously all numeric keys
press key acknowledge
Operation and indicator elements, mode of operation (PMI)
Meaning
password
year (yyyy)
date (dd.mm.)
time (hh.mm)
check sum user function
Meaning
password
year (yyyy)
date (dd.mm.)
time (hh.mm)
zone
Meaning
password entry
firmware version is displayed
D E L
. D E L .
. D E L .
0 0 0 0
possible at any time
when alarm or 15 sec. after last entry
Display (example)
P R O G
2 0 0 3
2 1.0 5.
1 5.3 7
8.2.3.6.
Display (example)
T E S T
2 0 0 3
2 1.0 5.
1 5.3 7
0 8
Display (example)
V._.6.1
static
flash simultaneously
static
flash for 15 sec.
A6V10265083_a_en_--
27
03.2010

Hide quick links: