Toshiba VFS5 Series Operation Manual page 14

Table of Contents

Advertisement

Display
Keypad Interface
Inverter/Motor
Protective functions
Protection from
instantaneous power
failure
Electronic thermal
characteristics
Enclosure
Type
Cooling method
Service environment
Ambient temperature
Relative humidity
Vibration
Climatic class
Polution degree
IP rating
TOSHIBA
Standard Specifications (cont'd)
4-digit, 7-segment LEDs w/8 discrete indicator lamps.
Stall prevention, current limit, overcurrent, overvoltage, output
short-circuit , overvoltage limit, undervoltage, electronic thermal
overload protection, armature overcurrent during starting,
overcurrent on load-side when starting-up, and emergency
stop (selection)
Auto-restart and regeneration power ride-through control
Standard motor and constant torque VF motor selectable;
overload trip and overload stall selectable
NEMA Type 1
Forced air cooling
Indoor. Altitude of < 1000m
Must not be exposed to direct sunlight, corrosive and/or explosive
gases or mists, fibers and dusts.
From -10°C to 40°C (14°F to 104°F).
93% maximum (non-condensating)
5.9 m/s (0.6G) maximum (10 to 55Hz)
3K3
2
2X
15

Hide quick links:

Advertisement

Table of Contents
loading