Setting the Environmental Functions (Maximum Frequency, Upper and Lower Limits, Base
Frequency, Etc. (cont'd)
Quick Setup Parameters (cont'd)
Parameter
Maximum frequency: FH
Upper limit frequency: Ul
Base frequency: ul
Frequency at VIA/II input
point 2: f204
Frequency at VIB input
point 2: f213
Auto restart: f301
Regeneration power
ride through control: f302
Source voltage
compensation: f307
Pattern of acceleration
and deceleration: f502
Manual drive environment setting
Set AU3 to 0, then set the parameters individually.
C A U T I O N
TOSHIBA
Description
Maximum output frequency of the drive
Upper limit frequency of the drive
Rated frequency of the motor
Output frequency when a 10 V voltage
command is input
Output frequency when a 10 V voltage
command is input
Operation restarts according to the
motor speed automatically if F-CC is
ON when the power is recovered from
instantaneous power failure.
In case of an instantaneous power
failure, the motor speed is reduced
automatically to continue operation.
Control is performed so that the output
voltage does not lower when the
source voltage drops.
An S pattern is used to accelerate and
decelerate the motor speed.
Do not set the maximum frequency above 80 Hz if the motor is a general-
purpose motor not designed for high-speed operation.
31
When AU3 is set to 1
When AU3 is set to 2
50 Hz
50 Hz
50 Hz
50 Hz
50 Hz
1: Instantaneous
power failure restart
control is effective
1: Instantaneous
power failure non-
stop control is
effective.
1:Source voltage.
compensation is
effective.
1:S pattern.
60 Hz
60 Hz
60 Hz
60 Hz
60 Hz
Same as left
Same as left
Same as left
Same as left