Standard Specifications - Toshiba VFS5 Series Operation Manual

Table of Contents

Advertisement

Major
Control System
Control
Output voltage regulation Same as power line.
Specifications
Output frequency range
Frequency setting
resolution
Frequency accuracy
Voltage/frequency
characteristics
Overload current rating
Frequency setting signal
PI control
Operation
Start frequency
functions
Frequency jump
PWM carrier frequency
Accel/decel time
Jogging run
Preset speed operation
Retry operation
Braking
DC braking
Output voltage regulation Drive can be programmed to set the maximum output voltage,
Input terminal functions
Output terminal functions Low-speed detection output signals, speed reached output
Fault signal
Output for frequency
counter or ammeter
TOSHIBA

Standard Specifications

Sinusoidal PWM control
0.5 to 320 Hz (0.5 to 80Hz default setting)*. Maximum frequency
is adjustable between 30 and 320 Hz.
0.1Hz input from the operating panel, 0.2 Hz analog
input (@ maximum frequency of 100 Hz).
Analog setting: ±0.5% of the maximum output frequency or less
@ 25°C±10°C,
Digital setting: ±0.01% of the maximum output frequency or less
@ -10°C to +50°C
Constant V/f, variable torque mode, sensorless vector control
mode, automatic torque boost mode, base frequency adjustment
(25 to 320Hz), and torque boost adjustment (0 to 30%).
150%, 60 seconds
Built-in potentiometer on the front panel, external potentiometer
(1k ohm to 10k ohm variable resistor connectable), 0 to 10Vdc
(input impedance: VIA = 30.55k ohm, VIB=30k ohm),
4 to 20mAdc (input impedance = 400 ohm), and optional
characteristics (gain,bias) can be preset by 2-point setting
Proportional gain, integral gain adjustments.
Adjustable between 0 and 10Hz
Three points (by setting jump frequencies and band widths)
Adjustable between 2.2 and 12kHz (default = 12kHz)
0.1 to 3600 secs, accel/decel time 1 or 2 selectable, S1 and S2
accel/decel pattern selectable
Jog run from panel with JOG mode selection. Terminal block
operation possible with parameter settings (see page 37).
Set frequency +15 preset speeds possible with open/closed
combinations of SS1, SS2, SS3, SS4 and CC
A maximum of ten automatic retries are selectable (see page 38)
Retry will occur immediately after a self evaluation of the main
circuit is completed.
Externally connected braking resistor (optional)
Braking start frequency (0 to max frequency), braking level
(0 to 100%), braking time (0 to 20 seconds).
float with the input voltage, or set the maximum output voltage to
the voltage sensed at power-up.
Forward and reverse input signals, preset speed select input
signals, reset input signals, and etc (see page 37).
signals, and etc.
1c contact output (250 Vac, 30 Vdc - 2A resistive load,
250 Vac, 30 Vdc - 1.5A inductive load, cosØ =0.4
Analog output (1 mA dc full scale ammeter or 7.5 Vdc, 1mA
full scale DC ammeter or rectifying AC voltmeter, 225% current
max., 1mA DC, 7.5 Vdc full scale)(see page 33)
14