6.2.4

Display and Metering Screens

The Powerware Energy Management System (EMS) provides Level Two and Level
Three display and metering configurations for the PDU:
S
Level Two metering includes system level input and output meters, Active Events
and History Logs, setup menu, mimic screen, Profile Log, and two X−Slot
communication bays.
S
Level Three metering has all the features of Level Two metering and includes
branch circuit or subfeed breaker level monitoring.
Level Two metering is the standard configuration for the PDU; Level Three metering
is optional.
6.2.5

Using the Menu

The PDU main menu bar allows you to display data in the information area to help you
monitor and control PDU operation. Table 6-2 shows the basic menu structure.
Table 6-2. Display Function Menu Map
Menu Option Description
EVENTS
METER
CONTROL
PROFILE
SETUP
®
EATON Powerware
225 kVA PDU Installation and Operation Manual
Displays the list of Active System Events and a historical log of system events.
Displays performance meters for the system or critical load.
Displays the Control screen to turn the PDU load off.
Displays load profile over a one−hour period for the most recent 24 months. Profile
includes highest and lowest input and output currents, frequencies, power levels, power
factors, AC undervoltage, and THD.
Allows the entry of a password, viewing the firmware version numbers, setting the
display contrast, changing the password, setting the date and time, clearing the history
screen, clearing the load profile screen, setting up a modem and the building alarms,
displaying the unit type, and changing the unit name. Available functions depend on the
setup level authorized.
Returns to main menu and mimic screen from the Events, Meter, Control, Profile, or
Setup screens. Returns to the main System Setup Level screen from a setup submenu.
Up or down arrows scroll through screens and lists or highlight settings.
Left or right arrows select or adjust settings displayed on the screen.
S
PDU OPERATING INSTRUCTIONS