Power Modules; Specifications Of The Power Modules - Honeywell ML200 Series Installation And Commissioning Manual

Table of Contents

Advertisement

Chapter 1 - Masterlogic components
Model Number
Specification
2MLP-ACF1
2MLP-ACF2
2MLP-AC23
2MLP-DC42
Table 2: Power modules for 2MLI CPUS/P
Model Number
2MLR-AC12
2MLR-AC22
2MLR-AC13
2MLR-AC23
2MLR-DC42
The specifications of the power modules for 2MLI CPUS/P and ML200R are the same. For more details,
refer to Table 5: Specifications of the power modules for ML200R .
The following table lists the specifications of the power modules for ML200-IEC.
Table 3: Specifications of the power modules for ML200-IEC
Items
Input
Rated input voltage
Input voltage range
Input frequency
Inrush current
Efficiency
Input fuse
Allowable
momentary
shutdown
Free Voltage (AC 110V,220V)/DC5V, 3A, DC24V,0.6A
Free Voltage(AC 110V,220V)/DC5V, 6A
AC 220V/DC 5V, 8.5A
DC 24V/DC 5V
Specification
Redundant power AC 110V, 5.5A
Redundant power AC 220V, 5.5A
Redundant power AC 110V, 8.5A
Redundant power AC 220V, 8.5A
Redundant power DC 24V, 7.5A
2MLP-
ACF1
AC 100V – AC 240V
AC 85V ~ AC 264V
50 / 60 Hz (47 ~ 63 Hz)
20 A peak or less
65% or more
Built-in (user no change), UL standard (Slow Blow
Type)
Within 20ms
2MLP-
2MLP-AC23 2MLP-DC42
ACF2
AC 200V –
AC 240V
AC 170V ~
AC 264V
- 3 -
DC 24V
-
-
80A peak or less
60% or more

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ml200rMl200-iecMl200

Table of Contents