Chapter 2 - Calculating the power supply for components
Example of current consumption/power calculations for ML200R
This section describes which power supply module must be used in coordination with the
corresponding modules for ML200R.
Main base
Type
CPU Module
Main Base
2MLR-M06P
CPU Module
Current Consumption / Power
Consumption
Expansion base
Type
Model
Expansion
2MLR-DBSF
Driver
Expansion
2MLR-E12P
Base
DI Module
2MLI-D24A
DO Module
2MLQ-RY2A
AI Module
2MLF-AD4S
Profibus-DP
2MLL-PMEA
Current Consumption/Power
Consumption
Sum of current consumption is 6.17A. Hence, use 2MLR-AC13 or 2MLR-AC23.
ATTENTION
Maximum power consumption of PLC can be derived from the efficiency of power module.
Example: Sum of 5V consumption x Minimum efficiency of Power module = 100W/0.65 = 154W.
The following figure illustrates the method used for calculating the current consumption of the PLC
system necessary for heat protection design.
Model
2MLR-CPUH/F
2MLR-M02P
1
2MLR-CPUH/F
Quantity
1
1
2
6
2
2
0.65A + 0.05A∗2 + 0.5A∗6 + 0.61A∗2 + 0.56A∗2 =
6.09ª / 6.09A × 5V = 30.85 W
Quantity
1
1
0.2A
1
1.31A + 0.61A∗6 = 4.97A/4.97×5V =
24.85W
Voltage (5V)
0.65A
0.21 A
0.05A
0.5A
0.61A
0.56A
- 20 -
Voltage (5V)
1.31A
0.2A
2MLR-M06P
1.31A