Honeywell ML200 Series Installation And Commissioning Manual page 59

Table of Contents

Advertisement

Code Error Causes
30
The module set in
parameter and
the actually
installed module
do not coincide
31
Module
detachment or
module addition
during operation
32
Fuse of a module
holding a fuse is
burnt out during
operation
33
IO module data
cannot be
successfully
accessed during
operation
Measures
Restart mode after the
measure.
reloaded, check the
storage condition and if
any fault is found,
replace the CPU
module.
Check the wrong slot
position by SoftMaster,
modify a module or
parameter, and then,
restart.
Reference flag: module
type inconsistence error
flag.
Check for
detached/added slot
position by SoftMaster,
modify the installment,
and restart (according to
parameter).
Reference flag: module
attachment error flag.
Check the position of a
slot of which fuse is burnt
out by SoftMaster,
replace a fuse and
restart (according to
parameter).
Reference flag: fuse
disconnection error flag.
Check the position of a
slot with access error by
SoftMaster, replace the
module and restart
(according to
parameter).
Reference flag: I/O
Module Write/Read
error flag.
- 57 -
Chapter 4 - Troubleshooting
Operation
LED
Status
Status
STOP
ERR : On
(RUN)
(P.S. :
On)
STOP
ERR : On
(RUN)
(P.S. :
On)
STOP
ERR : On
(RUN)
(P.S. :
On)
STOP
ERR : On
(RUN)
(P.S. :
On)
Diagnostic
Timing
Converting
to RUN
mode.
When the
scan ends.
When the
scan ends.
When the
scan ends.