Group 3.7: Prohibited Frequencies - Siemens BT300 Applications Manual

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Siemens Application
3.5.9

Group 3.7: Prohibited Frequencies

In some systems it may be necessary to avoid certain frequencies due to mechanical resonance prob-
lems. By setting up prohibit frequencies, it is possible to skip these ranges.
Code
Parameter
Prohibited frequency
P3.7.1
range 1 low limit
Prohibited frequency
P3.7.2
range 1 high limit
Prohibited frequency
P3.7.3
range 2 low limit
Prohibited frequency
P3.7.4
range 2 high limit
Prohibited frequency
P3.7.5
range 3 low limit
Prohibited frequency
P3.7.6
range 3 high limit
P3.7.7
Ramp time factor
24-hour support +1-800-877-7545 (Dial 2)
Table 37: Prohibited Frequencies.
Min
Max
Unit
-1,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,1
10,0
Times
Siemens Industry, Inc. • 47
Default
ID
0,00
509
0 = Not used
0,00
510
0 = Not used
0,00
511
0 = Not used
0,00
512
0 = Not used
0,00
513
0 = Not used
0,00
514
0 = Not used
Multiplier of the currently
1,0
518
selected ramp time between
prohibited frequency limits.
Description
3

Advertisement

Table of Contents
loading