Siemens BT300 Applications Manual page 82

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Siemens Industry, Inc. • 80
NOTE:
Long filtering time makes the regulation response slower!
Basic R01 function (P3.5.3.2.1)
Selection
Selection name
0
Not used
1
Ready
2
Run
3
General fault
4
General fault inverted
5
General alarm
6
Reversed
7
At speed
8
Motor regulator activated
9
Preset frequency active
10
Keypad control active
11
I/O control B active
12
Limit supervision 1
13
Limit supervision 2
14
Start command active
15
Reserved
16
Fire mode ON
17
RTC timer 1 control
18
RTC timer 2 control
19
RTC timer 3 control
20
FB Control WordB.13
21
FB Control WordB.14
22
FB Control WordB.15
23
PID1 in Sleep mode
%
Unfiltered signal
100%
63%
P3.5.2.2
Figure 21. AI1 signal filtering.
Table 56. Output signals via RO1.
The variable frequency drive is ready to operate
The variable frequency drive operates (motor is running)
A fault trip has occurred
A fault trip has not occurred
The reverse command has been selected
The output frequency has reached the set reference
One of the limit regulators (e.g. current limit, torque limit) is acti-
vated
The preset frequency has been selected with digital input
Keypad control mode selected
I/O control place B selected
Activates if the signal value falls below or exceeds the set super-
vision limit (P3.8.3 or P3.8.7) depending on the selected function.
Start command is active.
Time channel 1 is used.
Time channel 2 is used.
Time channel 3 is used.
Filtered signal
t [s]
11097.emf
Description