Group 3.1: Motor Settings - Siemens BT300 Applications Manual

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Siemens Industry, Inc. • 34
3.5.3

Group 3.1: Motor settings

3.5.3.1
Basic Settings
Code
Parameter
P3.1.1.1
Motor nominal voltage
Motor nominal fre-
P3.1.1.2
quency
P3.1.1.3
Motor nominal speed
P3.1.1.4
Motor nominal current
P3.1.1.5
Motor Cos Phi
P3.1.1.6
Motor nominal power
P3.1.1.7
Motor current limit
P3.1.1.8
Motor type
3.5.3.2
Motor Control Settings
Code
Parameter
P3.1.2.1 Switching frequency
P3.1.2.2 Motor switch
P3.1.2.4 Zero frequency voltage
Table 24: Basic motor settings.
Min
Max
Unit
Varies
Varies
V
8.00
320.00
Hz
24
19200
rpm
Varies
Varies
A
0.30
1.00
Varies
Varies
kW
Varies
Varies
A
0
1
Table 25: Advanced motor settings.
Min
Max
Unit
1.5
Varies
kHz
0
1
0.00
40.00
%
Siemens Application
Default
ID
Find this value U
rating plate of the motor.
This parameter sets the volt-
Varies
110
age at the field weakening
point to 100% * U
Note also used connection
(Delta/Star).
Find this value f
Varies
111
ing plate of the motor.
Find this value n
Varies
112
ing plate of the motor.
Find this value I
Varies
113
ing plate of the motor.
Find this value on the rating
Varies
120
plate of the motor
Find this value In on the rat-
Varies
116
ing plate of the motor.
Maximum motor current
Varies
107
from drive.
Select what motor type is
used. 0 = asynchronous
0
650
induction motor,
1 = PM synchronous motor.
Default
ID
Motor noise can be mini-
mized using a high switch-
ing frequency. Increasing
the switching frequency
reduces the capacity of the
Varies
601
drive. It is recommended to
use a lower frequency when
the motor cable is long in
order to minimize capaci-
tive currents in the cable.
Enabling this function pre-
vents the drive from tripping
when the motor switch is
0
653
closed and opened using
flying start for example.
0 = Disabled
1 = Enabled
This parameter defines the
zero frequency voltage of
Varies
606
the U/f curve. The default
value varies according to
unit size.
24-hour support +1-800-877-7545 (Dial 2)
Description
(V) on the
n
(V)
.
n
Motor
on the rat-
n
on the rat-
n
on the rat-
n
Description