Siemens Industry, Inc. • 40
3.5.7

Group 3.5: I/O Configuration

3.5.7.1
Digital inputs
Digital inputs are very flexible to use. Parameters are functions that are connected to the required digital
input terminal. The digital inputs are represented as, for example, DigIN Slot A.2, meaning the second
input on slot A.
It is also possible to connect the digital inputs to time channels which are also represented as terminals.
NOTE:
The status of digital inputs and the digital output can be monitored in the Multi-monitoring view,
see Chapter 3.4.1.
Code
Parameter
P3.5.1.1
Control signal 1 A
P3.5.1.2
Control signal 2 A
P3.5.1.3
Control signal 1 B
P3.5.1.4
Control signal 2 B
P3.5.1.5
I/O B control force
P3.5.1.6
I/O B reference force
P3.5.1.7
External fault close
P3.5.1.8
External fault open
P3.5.1.9
Fault reset
P3.5.1.10
Run enable
P3.5.1.11
Run interlock 1
P3.5.1.12
Run interlock 2
P3.5.1.13
Motor preheat ON
P3.5.1.14
Fire Mode activation
Preset frequency selec-
P3.5.1.15
tion 0
Preset frequency selec-
P3.5.1.16
tion 1
Preset frequency selec-
P3.5.1.17
tion 2
P3.5.1.18
Timer 1
P3.5.1.19
Timer 2
P3.5.1.20
Timer 3
P3.5.1.21
PID1 setpoint boost
P3.5.1.22
PID1 select setpoint
P3.5.1.23
PID2 start signal
Table 29: Digital input settings.
Default
ID
DigIN SlotA.1
403
Start signal 1 when control place is I/O 1 (FWD)
DigIN Slot0.1
404
Start signal 2 when control place is I/O 1 (REV)
DigIN Slot0.1
423
Start signal 1 when control place is I/O B
DigIN Slot0.1
424
Start signal 2 when control place is I/O B
DigIN Slot0.1
425
TRUE = Force the control place to I/O B
TRUE = Used frequency reference is specified
DigIN Slot0.1
343
by I/O reference B parameter (P3.3.4).
FALSE = OK
DigIN SlotA.3
405
TRUE = External fault
FALSE = External fault
DigIN Slot0.2
406
TRUE = OK
DigIN SlotA.6
414
Resets all active faults
DigIN Slot0.2
407
Must be on to set drive in Ready state
Drive will not start before this input is activated
DigIN Slot0.1 1041
(Damper interlock).
DigIN Slot0.1 1042 As above.
FALSE = No action
TRUE = Uses the motor preheat DC-Current in
DigIN Slot0.1 1044
Stop state
Used when parameter P3.1.2.5 is set to 2.
FALSE = Fire Mode active
DigIN Slot0.2 1596
TRUE = No action
Binary selector for Preset speeds (0-7). See
DigIN SlotA.4
419
page 38.
Binary selector for Preset speeds (0-7). See
DigIN SlotA.5
420
page 38.
Binary selector for Preset speeds (0-7). See
DigIN Slot0.1
421
page 38.
Rising edge starts Timer 1 programmed in Group
DigIN Slot0.1
447
3.11: Timer functions parameter group
DigIN Slot0.1
448
See above
DigIN Slot0.1
449
See above
FALSE = No boost
DigIN Slot0.1 1047
TRUE = Boost
FALSE = Setpoint 1
DigIN Slot0.1 1046
TRUE = Setpoint 2
FALSE = PID2 in stop mode
TRUE = PID2 regulating
DigIN Slot0.2 1049
This parameter will have no effect if PID2 control-
ler is not enabled in the Basic menu for PID2
Siemens Application
Description