Keypad of the drive
Before any parameters can successfully be copied from one drive to another, the drive has to be stopped
when the parameters are downloaded.
First go into User settings menu and locate the Parameter backup sub-menu.
In the Parameter backup sub-menu, there are three possible functions to be selected:
Restore factory defaults will re-establish the parameter settings originally made
at the factory.
By selecting Save to keypad you can copy all parameters to the keypad.
Restore from keypad will copy all parameters from the keypad to a drive.
STOP
READY
Main Menu
ID:
M6
I/O and Hardware
( 8 )
User settings
( 4 )
Favourites
( 0 )
NOTE:
If the keypad is changed between drives of different sizes, the copied values of these parame-
ters will not be used:
Motor nominal current (P3.1.1.4)
Motor nominal voltage (P3.1.1.1)
Motor nominal speed (P3.1.1.3)
Motor nominal power (P3.1.1.6)
Motor nominal frequency (P3.1.1.2)
Motor cos phii (P3.1.1.5)
Switching frequency (P3.1.2.1)
Motor current limit (P3.1.1.7)
Stall current limit (P3.9.12)
Stall time limit (P3.9.13)
Stall frequency (P3.9.14)
Maximum frequency (P3.3.2)
2.1.2.5
Help
The graphical keypad features instant help, and information displays for various items.
All parameters offer an instant help display. Select Help and press the OK button.
Text information is also available for faults, alarms and the startup wizard.
STOP
READY
Digital Inputs
ID:403
M3.5.1.1
Ctrl Signal 1 A
Ctrl Signal 2 A
Ctrl Signal 1 B
( 6 )
24-hour support +1-800-877-7545 (Dial 2)
Keypad
STOP
READY
User settings
ID:
Application selection
Parameter backup
( 3 )
Drive name
Figure 6. Parameter copy.
I/O
STOP
READY
ID:403
Edit
Help
Add to favorites
( 6 )
Figure 7. Help text example.
Keypad
STOP
M6.5
M6.5
HVAC
Drive
I/O
Ctrl signal 1 A
M3.5.1.1
Siemens Industry, Inc. • 11
READY
Keypad
Parameter backup
ID:
M6.5.1
M6.5
Restore factory defaults
Save to keypad
Restore from keypad
STOP
READY
Ctrl signal 1 A
ID:403
M3.5.1.1
Start Signal 1 for control Place
I/O A. Start Signal 1
functionality chosen with I/O A
Logic in Start/Stop Setup Menu.