Siemens BT300 Applications Manual page 19

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Keypad of the drive
2.2.5.2
Option board slots
The parameters of this group depend on the option board installed. If no option board is placed in slots
D or E, no parameters are visible. See Chapter 3.5.1 for the location of the slots.
When an option board is removed, info text "F39 Device removed" will display. See Table 3.7.3.
Menu
Slot D
Slot E
2.2.5.3
Real time clock
Table 5: I/O and Hardware menu, Real time clock parameters.
Code
Parameter
V5.4.1
Battery state
V5.4.2
Time
V5.4.3
Date
V5.4.4
Year
V5.4.5
Daylight saving
2.2.5.4
Power unit settings, Cooling Fan control
Code
Parameter
V5.5.1.1
Fan control mode
V5.5.1.3
Fan stop
The cooling fan operates in optimized or Always-On mode. In the optimized mode, fan speed is
controlled according to the drive's internal logic that receives data from temperature measurements (if
supported by the power unit) and the fan stops in 5 minutes when the drive is in Ready state.
In Always-On mode, the fan runs in full speed, without stopping.
24-hour support +1-800-877-7545 (Dial 2)
Function
Settings
Monitoring
Settings
Monitoring
Min
Max
1
3
1
4
Table 6: Power unit settings, Cooling Fan control.
Min
Max
0
1
0
1
Note
Option board related settings.
Monitor option board-related info.
Option board related settings.
Monitor option board-related info.
Unit
Default
ID
2
2205
hh:mm:s
2201 Current time of day
s
dd.mm.
2202 Current date
yyyy
2203 Current year
1
2204
Unit
Default
ID
1
2377
1
Siemens Industry, Inc. • 17
Description
Status of battery.
1 = Not installed
2 = Installed
3 = Change battery
Daylight saving rule
1 = Off
2 = EU
3 = US
4 = Russia
Description
0 = Always On
1 = Optimized
If enabled, the fan will stop
after 5 minutes when the
drive is in Ready state.
0 = Disabled
1 = Enabled
2