Group 3.3: Control Reference Settings - Siemens BT300 Applications Manual

Hvac drive
Hide thumbs Also See for BT300:
Table of Contents

Advertisement

Siemens Application
3.5.5

Group 3.3: Control reference settings

The frequency reference source is programmable for all control places except PC, which always takes
the reference from the PC tool.
Auto control place (I/O A): The source of frequency reference can be selected with parameter P3.3.3.
Auto control place (I/O B): The source of frequency reference can be selected with parameter P3.3.4.
Hand control place (Keypad): If the default selection for parameter P3.3.5 is used the reference set
with parameter P3.3.6 applies.
Auto control place (Fieldbus): The frequency reference comes from fieldbus if the default value for pa-
rameter P3.3.9 is kept.
Code
Parameter
P3.3.1
Minimum frequency
P3.3.2
Maximum frequency
I/O control reference A
P3.3.3
selection
I/O control reference B
P3.3.4
selection
Keypad Ctrl Reference
P3.3.5
selection
P3.3.6
Keypad reference
P3.3.7
Keypad direction
P3.3.8
Keypad reference copy
24-hour support +1-800-877-7545 (Dial 2)
Table 27: Control reference settings.
Min
Max
Unit
0.00
P3.3.2
Hz
P3.3.1
320.00
Hz
1
8
1
8
1
8
0.00
P3.3.2
Hz
0
1
0
2
Siemens Industry, Inc. • 37
Default
ID
Minimum allowed frequency
0.00
101
reference
Maximum allowed frequency
60.00
102
reference
Selection of ref source when
control place is I/O A
1 = Preset Frequency 0
2 = Keypad reference
3 = Fieldbus
6
117
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer
Selection of ref source when
control place is I/O B. See
above.
4
131
NOTE: I/O B control place can
only be forced active with digi-
tal input (P3.5.1.5).
Selection of ref source when
control place is keypad:
1 = Preset Frequency 0
2 = Keypad
3 = Fieldbus
2
121
4 = AI1
5 = AI2
6 = AI1+AI2
7 = PID 1 reference
8 = Motor potentiometer
The frequency reference can
0.00
184
be adjusted on the keypad
with this parameter.
Motor rotation when control
place is keypad
0
123
0 = Forward
1 = Reverse
Selects function for Run state
& Reference copy when
changing to Keypad control:
1
181
0 = Copy reference
1 = Copy ref & Run State
2 = No copying