Module; Troubleshooting For The Module As00Scm As A Communication Module12-23 - Delta AS Series Operation Manual

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

Type
IO-Link
Event
Warning Error
Codes
0xFF24
0xFF25
12.3.6 Troubleshooting for the Module AS00SCM as a Communication

Module

12.3.6.1
ERROR LED Indicators Are ON
The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU
module and acts as a communication module.
Error
Code
16#1605
Hardware failure
16#1606
The function card setting is incorrect.
12.3.6.2
ERROR LED Indicators Blinking Every 0.5 Seconds
The following error codes identify possible errors when the AS00SCM module is installed on the right side of the CPU
module and acts as a communication module.
Error
Code
16#1802
Incorrect parameters
16#1803
Communication timeout
16#1804
The UD Link setting is incorrect.
The following error codes can only be viewed with SCMSoft; when the following errors occur, they are not shown on the
LED indicators and the system does not send the error messages to the CPU module.
Error
Code
The settings in HWCONFIG and manual
16#0107
settings are not consistent with function
card 1.
Event
Notifica-
tion
V
Data storage not sufficient
Data storage parameter
V
access denied
Description
Description
Description
C h a p t e r 1 2 Tr o u b l e s h o o t i n g
Solution
Check device
specifications
Check device
specifications
Solution
1.
Check that the module is securely installed.
2.
Install a new AS00SCM or contact the factory.
1.
Check if the function card is securely installed.
2.
Install a new function card or contact the factory.
3.
Check if the setting in HWCONFIG is consistent with
the function card setting.
4.
Install a new AS00SCM or contact the factory.
Solution
Check the parameter in HWCONFIG. Download the
parameter again.
1.
Check whether the communication cable is
properly connected.
2.
Check if the station number and the
communication format are correctly set.
3.
Check if the connection with the function card is
working correctly.
1.
Check the settings of the UD Link.
2.
Check the warning settings in the PLC.
Solution
Check the settings in HWCONFIG and manual
settings for function card 1.
Source
IO-Link
IO-Link
Master
Device
V
V
12_
1 2 - 2 3