Delta AS Series Operation Manual page 69

Hide thumbs Also See for AS Series:
Table of Contents

Advertisement

A S S e r i e s O p e r a t i o n M a n u a l
_2
Analog-to-Digital
Conversion
Rated Input Range
Rated Conversion
Range
Hardware Input
-20.24 mA ~ 20.24 mA
1
Limit*
2
Conversion Limit*
Error Rate
Hardware Resolution
Input Impedance
Absolute Input
3
Range*
*1: If the input signal exceeds the hardware input limit, the module only shows the maximum value. If the
input signal is below the lower limit, it only shows the minimum value.
*2: If the input signal exceeds the hardware input limit, it also exceeds the conversion limit and a
conversion limit error appears. For example in the voltage input mode (4 mA to 20 mA), when the input
signal is 0 mA, exceeding the hardware upper limit, it also exceeds the conversion upper limit. The
module uses the upper limit value (-384) as the input signal and a conversion limit error appears.
*3: If an input signal exceeds the absolute range, it might damage the channel.
AS04DA-A
Electrical specifications
Module name
Number of outputs
Digital-to-analog
conversion
Supply voltage
Connector type
Conversion time
An analog circuit is isolated from a digital circuit by a digital integrated circuit/an
optocoupler, but the analog channels are not isolated from one another.
Isolation between a digital circuit and a ground: 500 VDC
Isolation
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC
Weight
Current Input
±20 mA
0 mA–20 mA
K-32000
~
K+2000
K32000
-0.24 mA ~ 20.24 mA
K-32384
~
K32384
K32384
Room Temperature: ±0.2% ; Full Temperature Range: ±0.5%
AS04DA-A
Voltage output/Current output
24 VDC (20.4 VDC–28.8 VDC) (-15%–+20%)
Removable terminal block
2 ms/channel
4 mA–20 mA
K0
~
K32000
3.81 mA ~ 20.19 mA
K-384
K-384
~
K32384
16 bits
250Ω
±32 mA
Four
145 g
K0
~
~
2 - 3 5