Siemens SINAMICS G120C Getting Started page 50

Frequency converter
Hide thumbs Also See for SINAMICS G120C:
Table of Contents

Advertisement

Trouble shooting
5.1 List of alarms and faults
Number
Cause
F30011
Line phase failure
F30015
Motor cable phase failure
F30021
Ground fault
F30027
Time monitoring for DC link pre-
charging
F30035
Overtemperature, intake air
F30036
Overtemperature, inside area
F30037
Rectifier overtemperature
A30049
Internal fan defective
F30059
Internal fan defective
F30074
Communications fault between
Control Unit and Power Module
A30502
DC link overvoltage
A30920
Temperature sensor fault
A50001
PROFINET configuration error
A50010
PROFINET name of station
invalid
A50020
PROFINET: Second controller
missing
For further information, please refer to the List Manual.
48
Remedy
Check the converter's input fuses.
Check the motor cables.
Check the motor cables.
Increase the ramp-up or ramp-down time (p1120).
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might be
broken).
Check the supply voltage on the input terminals.
Check the line voltage setting (p0210).
Check whether the fan is running.
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
See F30035 and, in addition:
Check the motor load.
Check the line phases
Check the internal fan and if required replace.
Check the internal fan and if required replace.
The 24V voltage supply of the converter (terminals 31 and 32) was
interrupted briefly.
Please check the voltage supply and the wiring.
Check the device supply voltage (p0210).
Check the line reactor dimensioning
Check that the sensor is connected correctly.
A PROFINET controller is attempting to establish a connection with a faulty
configuration telegram. Check to see whether "Shared Device" is activated
(p8929 = 2).
Correct name of station (p8920) and activate (p8925 = 2).
"Shared Device" is activated (p8929 = 2). However, only the connection to a
PROFINET controller is present.
SINAMICS G120C frequency converter
Getting Started, 03/2012, FW V4.5, A5E03831830B AA

Hide quick links:

Advertisement

Table of Contents
loading