3.1

Mechanical installation

Table 3- 1
Dimensions, drill patterns and minimum distances
Distances to other equipment:
SINAMICS G120C frequency converter
Getting Started, 03/2012, FW V4.5, A5E03831830B AA
Frame Size A
0.55 kW ... 4.0 kW
Height
196 mm
Width
73 mm
Depth of the
225.4 mm
converter with
PROFINET
interface
Depth of the
203 mm
converter with
USS/MB,
CANopen or
PROFIBUS
interface
+ Depth
Drill pattern
Fixings
3 × M4 bolts
3 × M4 nuts
3 × M4 washers
Tightening
2.5 Nm
torque
Frame Size B
5.5 kW ... 7.5 kW
196 mm
100 mm
225.4 mm
203 mm
+ 21 mm supplementary depth with the operator
panel IOP snapped onto the converter.
+ 6 mm supplementary depth with the operator
panel BOP-2.
4 × M4 bolts
4 × M4 nuts
4 × M4 washers
2.5 Nm
3
Frame Size C
11 kW ... 18.5 kW
295 mm
140 mm
225.4 mm
203 mm
4 × M5 bolts
4 × M5 nuts
4 × M5 washers
2.5 Nm
9