Commissioning
4.2 Further settings
P-No.
Note
p1037
Motorized potentiometer maximum speed [rpm]
p1038
Motorized potentiometer minimum speed [rpm]
p1040
Motorized potentiometer start value [rpm]
p1043
BI: Motorized potentiometer, accept setting value
p1044
CI: Motorized potentiometer setting value [100 %
≙ p2000]
r1045
CO: Motorized potentiometer, setpoint in front of
the ramp-function generator [rpm]
p1047
Motorized potentiometer ramp-up time [s]
p1048
Motorized potentiometer ramp-down time [s]
r1050
CO: Motorized potentiometer setpoint after the
ramp-function generator [100 % ≙ p2000]
p1055
BI: Jog bit 0
p1056
BI: Jog bit 1
p1058
Jog 1 speed setpoint [rpm]
p1059
Jog 2 speed setpoint [rpm]
p1070
CI: Main setpoint [100 % ≙ p2000]
p1071
CI: Main setpoint scaling [100 ≙ 100%]
r1073
CO: Main setpoint effective [100 % ≙ p2000]
p1075
CI: Supplementary setpoint [100 % ≙ p2000]
p1076
CI: Supplementary setpoint scaling [100 ≙ 100%]
r1077
CO: Supplementary setpoint effective
[100 % ≙ p2000]
r1078
CO: Total setpoint effective [100 % ≙ p2000]
p1080
Minimum speed [rpm]
p1082
Maximum speed [rpm]
p1083
CO:Speed limit in positive direction of rotation
[rpm]
r1084
CO: Speed limit positive effective [100 % ≙
p2000]
p1086
CO: Speed limit in negative direction of rotation
[rpm]
r1087
CO: Speed limit negative effective [100 % ≙
p2000]
p1091
Skip speed 1 [rpm]
p1092
Skip speed 2 [rpm]
p1101
Skip speed bandwidth [rpm]
p1110
BI: Inhibit negative direction
p1111
BI: Inhibit positive direction
p1113
BI: Setpoint inversion
r1114
CO: Setpoint after the direction limiting [100 % ≙
p2000]
r1119
CO: Ramp-function generator setpoint at the input
[100 % ≙ p2000]
32
P-No.
Note
p1120
Ramp-function generator ramp-up time [s]
p1121
Ramp-function generator ramp-down time [s]
p1130
Ramp-function generator initial rounding-off time
[s]
p1131
Ramp-function generator final rounding-off time
[s]
p1134
Ramp-function generator rounding-off type
0
Continuous smoothing
1
Discontinuous smoothing
p1135
OFF3 ramp-down time [s]
p1136
OFF3 initial rounding-off time [s]
p1137
OFF3 final rounding-off time [s]
p1138
CI: Acceleration ramp scaling [100 ≙ 100%]
p1139
CI: Deceleration ramp scaling [100 ≙ 100%]
p1140
BI: Enable ramp-function generator
p1141
BI: Continue ramp-function generator
p1142
BI: Enable speed setpoint
r1149
CO: Ramp-function generator acceleration
[100 % ≙ p2007]
r1170
CO: Speed controller setpoint sum
[100 % ≙ p2000]
r1198
CO/BO: Control word, setpoint channel
p1200
Flying restart operating mode
0
Flying restart inactive
1
Flying restart always active (start in setpoint
direction)
4
Flying restart always active (start only in
setpoint direction)
p1201
BI: Flying restart enable signal source
p1202
Flying restart search current [100 % ≙ r0331]
p1203
Flying restart search rate factor [%]
A higher value results in a longer search time.
p1206
Set fault number without automatic restart
p1210
Automatic restart mode
Getting Started, 03/2012, FW V4.5, A5E03831830B AA