Commissioning

4.1 Basic commissioning with BOP-2

4.1
Basic commissioning with BOP-2
The basic commissioning sets the most important data of the drive.
1.
2.
3.
4.
5,
6.
7.
8.
9.
10.
11.
22
The "SETUP" menu guides you step by step through the basic
OK
commissioning of the drive.
Select Reset if you wish to reset all parameters to the factory setting
OK
before the basic commissioning: nO → YES → OK
Select the motor control mode. The most important control modes
OK
are:
VF LIN
VF QUAD
SPD N EN
IEC or
OK
NEMA
standard
Voltage
OK
Current
OK
Power
OK
IEC (kW)
Power
NEMA (HP)
Speed
OK
We recommend the setting STIL ROT (Identify motor data at
OK
standstill and with the motor rotating).
If one of the following cases applies, select the setting STILL (identify
motor data at standstill):
 You have selected the "Speed control" control mode, but the
motor cannot rotate freely, e.g. for mechanically limited traversing
sections.
 You have set "V/f control" as control mode.
Select the configuration for the inputs and outputs, as well as the
OK
correct fieldbus for your application. The predefined configurations
can be found in the section titled Pre-defined interface configurations
(Page 14).
Set the minimum motor speed.
OK
Set the motor ramp-up time.
OK
V/f control with linear characteristic
V/f control with square-law characteristic
Closed loop speed control (vector control)
D-91056 Erlangen
D-91056 Erlangen
3~Mot. 1LE10011AC434AA0
3~Mot. 1LE10011AC434AA0
IEC/EN 60034 100L
IEC/EN 60034 100L
IMB3
IMB3
25 kg
25 kg
Th.Cl. 155(F)
Th.Cl. 155(F)
-20°C
-20°C
Tamb
Tamb
Bearing
Bearing
UNIREX-N3
UNIREX-N3
DE
DE
6206-2ZC3
6206-2ZC3
15g
15g
NE
NE
6206-2ZC3
6206-2ZC3
11g
11g
60Hz:
60Hz:
SF 1.15 CONT
SF 1.15 CONT
V
Hz
A
kW
PF
400
50
3.5
1.5
0.73
690
Y
50
2.05
1.5
0.73
460
60
3.15
1.5
0.69
Set the motor data on the rating plate
Getting Started, 03/2012, FW V4.5, A5E03831830B AA
E0807/0496382_02 003
E0807/0496382_02 003
IP55
IP55
40°C
40°C
Intervall: 4000hrs
Intervall: 4000hrs
NEMA
NEMA
MG1-12
MG1-12
TEFC
TEFC
Design A
Design A
2.0 HP
2.0 HP
NOM.EFF
NOM.EFF
rpm
V
V
84.5%
84.5%
970
380 - 420
380 - 420
3.55-3.55
3.55-3.55
84.5%
84.5%
970
660 - 725
660 - 725
2.05-2.05
2.05-2.05
86.5%
86.5%
1175
SINAMICS G120C frequency converter
A
A
CL
CL
K
K