Siemens IM 328–N Description page 53

Sinumerik 805sm/840c link to sinec l2–dp
Table of Contents

Advertisement

07.96
3.3.3
Procedure for installation and startup
The following procedure is recommended for installation and startup of a
SINEC L2–DP slave module:
1. Set and check the following data on the module in accordance with
2. Install the module in the control
3. Modify the configuration of the master (IM 308–B):
Siemens AG 1996 All Rights Reserved
SINUMERIK 805SM / 840C (BS)
3.3 Description of the L2-DP slave up to V3.x
Sections 2.1.1 and 2.2.1:
Bus interface
Address range (number of input and output bytes)
Module number (base address) and
Address window.
Switch off the control
Plug the module into a valid slot (see [2], [3] or [4])
Set the station address on the front panel in accordance with Sections
2.1.2 and 2.2.2.
Connect the module to the SINEC L2–DP field bus
Switch on the control (POWER ON) and perform a RESTART of the
PLC if required.
Add the configuration data of the new station to the existing program
file
Write the memory module for the IM 308–B
Program and activate monitoring and diagnostics functions on the
master and slave sides.
6ZB5 430–0BH02–1AA0
Description
3-25
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Im 329–n

Table of Contents