FUNCTION
Power supply cable
Relay output cables
Serial connection wire
Power connection cable
Thermocouple input probe
"PT100" temperature resistance input probe
Generic standards, emission standard for residential
commercial and light industrial environments
Emission enclosure
Emission AC mains
Radiated emission
Generic standards, immunity standard for industrial
environments
Immunity ESD
Immunity RF interference
Immunity conducted disturbance
Immunity burst
Immunity pulse
Immunity Magnetic fields
Voltage dips, short interruptions and voltage immunity tests
Safety requirements for electrical equipment for measurement,
control and laboratory use
EMC conformity has been tested with the following connections
EMC Emission
EMC Immunity
CABLE TYPE
1 mm
2
1 mm
2
0,35 mm
2
see related sections
0,8 mm
2
compensated
1 mm
2
Table 1
CEI EN 61000-6-3
CEI EN 61000-6-3
CEI EN 61000-6-3
CEI EN 61326 CISPR 16-2
CEI EN 61000-6-2
CEI EN 61000-4-2
CEI EN 61000-4-3 /A1
CEI EN 61000-4-6
CEI EN 61000-4-4
CEI EN 61000-4-5
CEI EN 61000-4-8
CEI EN 61000-4-11
LVD Safety
CEI EN 61010-1
24
LENGTH
1 mt
3,5 mt
3,5 mt
3.5 mt
5 mt
3 mt
Group1 Class B
Group1 Class B
Class B
4 kV contact discharge level 2
8 kV air discharge
level 3
10 V/m amplitude modulated
80 MHz-1 GHz
10 V/m amplitude modulated
1.4 GHz-2 GHz
10 V/m amplitude modulated
0.15 MHz-
80 MHz (level 3)
2 kV power line (level 3)
2 kV I/O signal line (level 4)
Power line-line 1 kV (level 2)
Power line-earth 2 kV (level 3)
Signal line-earth 1 kV (level 2)
100 A/m (level 5)
100%U, 70%U, 40%U,